Place of Origin: | China (Mainland) |
---|---|
Brand Name: | ghorit |
Model Number: | GVS16-40.5 |
Type: | Vacuum |
Poles Number: | 3 |
certificate: | ISO9001 |
rated voltage: | 40.5kv |
rated frequency: | 50hz |
Quick Details
Specifications
GVS16-40.5 Series Embedded Poles Handcart Type Vacuum Circuit Breaker
GVS16-40.5 series embedded poles handcart type vacuum circuit breaker, apply for rated voltage 24kV, frequency 50Hz three-phase AC power system, widely used in power plants, transformer substation, petrochemical, metallurgical, manufacturing, airport And communities , use for electrical facilities' protection and control, especially for frequently operating under the rated current Or more times for short-circuit current interrupting the place. With the VD4, VEP circuit breaker full realization of interchangeable. Can be installed on the away-style or fixed air-insulated switchgear cabinet. The product accordance to GB1984 AC high voltage circuit breaker ;, DL/T403 12 ~ 40.5kV Indoor AC high-voltage circuit breaker order technical condition ; and IEC60694, IEC6227-100 and other related standards.
GVS16-40.5 series embedded poles handcart type vacuum circuit breaker adapt to APG advanced technology, directly to put the vacuum interrupter Room and lead electrical circuit solid seal in epoxy resin post then become the way of solid sealing insulation, represents the highest level of the design and manufacture of high voltage vacuum circuit breaker today world.
Note: This models vacuum interrupter chamber seal replaced with ordinary insulation tube column installation method, the model GVS16-40.5P.
The Use of Environmental Conditions:
1. Altitude: not exceed 2000m.
2. Ambient temperature: not higher than +40 Celsius, not less than -15 Celsius
3. Relative humidity: daily average of not more than 95%, month average of not more than 90%.
4. Earthquake intensity: not more than eight.
5. The ambient air without water drop, no fire, explosion hazard, serious filthy, chemical corrosion as we as places of intense vibration.
Mainly Technical Parameters:
NO. | Item | Units | Parameters | |
1 | Rated voltage | kV | 40.5 | |
2 | Rated Frequency | Hz | 50 | |
3 | Rated Lightning Impulse voltage tolerance(peak) | kV | 185 | |
4 | Rated short-time power-frequency voltage tolerance(1min) | kV | 95 | |
5 | Rated current | A | 630, 1250, 1600 | 1600, 2000, 2500 |
6 | Rated short-circuit breaking current | kA | 25 | 31.5 |
7 | Rated short-circuit closing current (peak) | kA | 63 | 80 |
8 | Rated short-circuit duration time | S | 4 | |
9 | Rated operating sequence | 0-0.3s-CO-180s-CO | ||
10 | Rated a single / back-to-back electric current breaking device group | A | 630/400 | |
11 | Rated short-circuit breaking current breaking number | times | 30 | |
12 | Closing time | ms | ≤ 75 | |
13 | Opening time | Times | ≤ 65 | |
14 | Mechanical life | V | 10000 | |
15 | Rated Storage and operation voltage | mm | AC DC 220/110 | |
16 | Contact distance | mm | 18±2 | |
17 | Contact Over travel | mm | 7.5±1.5 | |
18 | Average Closing speed | m/s | 0.7±0.2 | |
19 | Average opening speed | m/s | 1.6±0.2 | |
20 | Contact closing spring time | ms | ≤3 | |
21 | Three phase closing opening asynchrony | ms | ≤2 | |
22 | Lead circuit resistance | υΩ | ≤50(630A, 1250A) ≤35(1600~2000A)≤30(2500A) |