Product Main

Quick Details

Place of Origin: Japan
Brand Name: YOKOGAWA EJA
Model Number: Differential Pressure Transmitter EJA 210/220 A
Accuracy: 0.2%
Degrees of protection: IP67, NEMA 4X, and JIS C0920 immersion proof
Process temperature: -40 to 120 deg C (-40 to 248 deg F) (general use type)
Maximum working pressure: Flange rating pressure
Mounting: Flange mounting
Housing: Cast aluminum alloy or SUS316 equivalent stainless steel (optional

Specifications

Differential Pressure Transmitter EJA 210/220 A Japan


The high performance flange mounted differential pressure transmitter models EJA210A and 220A can be used to measure levels of densities of solidifying or precipitating liquids. Both output a 4 to 20 mA DC signal corresponding to the measured differential pressure.

The EJA Series is available with BRAIN, HART, FOUNDATION? fieldbus or PROFIBUS PA communication protocols.


Features
Excellent performance and stability

The EJA series uses a silicon resonant sensor formed from monocrystal silicon, a perfect material which has no hysteresis in pressure or temperature changes. The sensor minimizes overpressure, temperature change, and static pressure effects, and thus offers unmatched long-term stability.


Compact and light-weight design
Half the weight of conventional models thanks to miniaturization of the casing with the amplifier ASIC, pressure cell structure, and flange. The ASIC uses the minimum number of parts and improves the reliability of the amplifier.


Fieldbus communication capability
Fieldbus is a digital two-way communication system. It is a revolutionary technology for configuring instrumentation control systems and a promising successor to the standard 4 to 20 mA analog communication used in most field instruments today.

EJA series offers two types of fieldbus models, FOUNDATION? fieldbus Low Voltage Mode and PROFIBUS PA devices, which ensure interoperability between Yokogawa and other manufactures. As for software, the EJA series incorporates two AI function blocks that compute differential and static pressures to allow flexible configuration of instrumentation.



EJA210A / EJA220A
Liquid Level Differential Pressure Transmitter
M Capsule
H Capsule
Range
-100 to 100 kPa
(-400 to 400 inH 2 O)
-500 to 500 kPa
(-2000 to 2000 inH 2 O)
Span
1 to 100 kPa
(4 to 400 inH 2 O)
5 to 500 kPa
(20 to 2000 inH 2 O)
Accuracy
±0.2%
±0.2%
Degrees of protection
IP67, NEMA 4X, and JIS C0920 immersion proof
Certificates
FM, CENELEC ATEX, CSA, IECEx
Output
4 to 20 mA DC or FOUNDATION? fieldbus or PROFIBUS PA 2-wire system with digital communication
Supply voltage
BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type)
Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model)
Ambient temperature
-40 to 85 deg C (-40 to 185 deg F) (general use type)
-30 to 80 deg C (-22 to 176 deg F) (with integral indicator)
Process temperature
-40 to 120 deg C (-40 to 248 deg F) (general use type)
Maximum working pressure
Flange rating pressure
Mounting
Flange mounting
Process flange size
EJA210A: 3-inch (80mm), 2-inch (50mm)
EJA220A: 4-inch (100mm), 3-inch (80mm)
Diaphragm material
(High side)
SUS316L, Hastelloy C-276, Tantalum
Process flange material
S25C, SUS304, SUS316
Housing
Cast aluminum alloy or SUS316 equivalent stainless steel (optional