Specifications

AAC  AAAC   ACSR

Specifications

ACSR/AAC/AAAC/ACAR aluminum strand overhead conductor
1.8 years factory product
2.good feature
3.delivery fast

ACSR,AAC,AAAC,ASCSR&ACAR conductor widely used in power transmission lines with various voltage levels.

 

Specification:

(1) all aluminum conductor (AAC)

(2) all aluminum alloy conductor(AAAC)

(3) aluminum conductor steel reinforced (ACSR)

(4) anti-corrosion type ACSR

(5) aluminum conductor aluminum clad steel reinforced(ACSR/AW)

(6) rear earth aluminum conductor steel reinforced(ACSR/RE)

(7) aluminum conductor aluminum alloy reinforced(ACAR)


 

ACSR Conductor

ACSR is a composite concentric-lay-stranded conductor. Galvanized steel strand or strands form the central core of the conductor, around which is stranded one or more layers of EC Grade Aluminum wires. The steel core may consist of a single strand or a concentric stranded cable of 7, 19, 37, or more wires. Numerous combinations of aluminum and steel strands and layers are possible.

 

1. Applications

Conductor(AAC and ACSR) have been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance, low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.

 

2. Service Performance

(1).The permissible long-time operating temperature for aerial conductor is 70oC.

(2).Under the circumstance that rare climate is occurring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.

(3).When connecting conductors, the conductor beside the connecting tube cant be prominent. Otherwise, the force on the operating conductors will be unbalanced. After connectors are installed, the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.

(4).Under installation,the arc downing stress of all the conductors should be the same. With in the permissible distance of crossing buildings or dropping to the ground, the stress can be 10-15% higher than regular stress.

 

3.Product Performance

(1).The electrical performance of AAC and ACSR is indicated in DCΩ/km(20oC).The resistivity of the hard aluminum wire for stranded wires is not greater than 28.264 nΩ. m of international standard value.

(2).The rated tensile strength of AAC is denoted with the result of total cross-section of all aluminum conductors multiplied by min.tensile of corresponding size specified in the standard for aluminum wire.

(3).The rated tensile strength of ACSR is denoted with sum of all aluminum conductor tensile strength and steels tensile strength.

a.The tensile strength of all aluminum conductors is denoted with the result of all cross-sections of aluminum conductors multiplied by min.tensile strength of corresponding size specified in the standard for aluminum wire.

b.The tensile strength of all steel wire is denoted with the result of all cross-sections of steel wires multiplied by the stress at 1% elongation of corresponding size specified in the standard for steel wire.

 

4.Material Standard

(1).The hard aluminum conductor used for AAC and ACSR conforms to the standard GB/T 17048-1997(equivalent to IEC 60889:1987).

(2).The zinc coated steel wire used for ACSR conforms to IEC 60888:1987.

(3).Production can be arranged according to customers requirements for material standard,etc.

Construction of All Aluminum Conductor and Aluminum Conductor Steel Reinforced

 

Standards:

ASTM-B232   Standard specification for Concentric-Lay-Stranded Aluminum 1350 Conductors

BS215-2       aluminum conductors steel-reinforced —For overhead power transmission

DIN48204       Steel reinforced aluminum stranded conductors

IEC209           Aluminum stranded conductor steel reinforced

Customized type available.

 

ACSR Technical Characteristics Based on Standard BS 215-2

Code name

Nominal aluminum area

Stranding and wire diameter

Sectional area of aluminum

Total sectional area

Approx. overall diameter

Approx. mass

Calculated D.C. resistance at 20oC

Calculated breaking load

Al

Steel

mm2

No./mm

mm2

mm2

mm

kg/km

Ω/km

kN

RABBIT

50

6/3.35

1/3.35

52.88

61.7

10.05

214

0.5426

18.35

DOG

100

6/4.72

7/1.57

105

118.5

14.15

394

0.2733

32.7

WOLF

150

30/2.59

7/2.59

158.1

194.9

18.13

726

0.1828

69.2

DINGO

150

18/3.35

1/3.35

158.7

167.5

16.75

506

0.1815

35.7

LYNX

175

30/2.79

7/2.79

183.4

226.2

19.53

842

0.1576

79.8

ZEBRA

400

54/3.18

7/3.18

428.9

484.5

28.62

1621

0.0674

131.9