Place of Origin: | China (Mainland) |
---|---|
Brand Name: | smartsimple or oem |
Model Number: | TC-ALD-302 |
Quick Details
Specifications
Functions
The products are mainly used for leaking sensitive occasions,such as the engine room,grain storage,etc.By deploying liquid leakage sensor rope under air conditioning pipes in the engine room and other possible leaks region,and monitoring the whole thread. When it detects a leak, it will issue a warning,convenient for managers handle leaks timely.The module can be integrated into the monitoring platform to view detailed data.
Applications
1) Using for detecting leakage of air conditioning pipes in the engine room;
2) Using for detecting leakage in the grain storage.
Main Features
? Beautiful appearance, standard structure,and rail mounting;
? Panel operating, multi-state instructions,convenient to use;
? Using the button to set the sensitivity(three levels sensitivity),cancel the alarm,and restore factory settings;
? Smart delay,effectively prevent false alarm
? Support RS485 communication, it can be integrated into monitoring platform and recording detailed data;
? Using standard modbus communication protocol,application widely;
? Two independent leakage detection interfering;
? Support switch alarming output (output per channel individually), Normally open or normally closed Can be Configuration.
Specifications
Main Part | |
Brand Name | ZHT(ZongHengTong) |
Model No. | TC-ALD-302 |
Color | Blue |
Specifications | |
DetectionChannels | 2 ways(independent) |
Monitoring Range | 500m |
Communication Interface | RS485,1 way |
Communication Address | 1~255, default:1 |
Communication Rate | 2400bps,4800bps,9600bps,19200bps, default:9600bps |
Alarm Output Type | switch signal(normally open or closed),2 ways(independent) |
Supply Voltage | 5.5VDC~18VDC,Rated voltage: 12VDC |
Power Consumption | ≤0.75W |
WorkingEnvironment | -20℃~70℃ , 0~100%RH,no condense |
Mounting Method | Rail mounting |
Size(L×W×H) | (100+20)mm×70mm×(25+15)mm |
Weight | 125g |