| Brand Name: | zc |
|---|---|
| Product name: | addressable heat detector |
| Model Number: | 920E |
| Place of Origin: | China (Mainland) |
| Executive standard: | GB4716-2005 |
| Operating voltage: | 24V (pulse modulation) |
| Wiring method: | non-polarity two-bus system (L1, L2) |
| Protection area: | about 60m2. |
| Installation height: | <8m |
Quick Details
Specifications
Skype firealarm87 /wechat 15220176087
I. Product overview
the detector is suitable for such industrial and civil Buildings that have a great deal of heat when fire takes place, such as Kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and Is not suitable for places with a great deal of smoke but little heat.
II. Product features
It can realize electronic coding and rewrite the address via Coder in situ.
Within a single-chip microcomputer, it can realize real-time Data acquisition and processing, realize a curve tracing for the field Situation.
It has a temperature compensation function and a sensor fault Detection function (fault reporting to fire Alarm control panel).
Non-polarity, two-bus connection that ensures Convenient installation and maintenance.
Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained Conveniently.
III. Technical parameters
1. Executive standard: GB4716-2005
2. Operating voltage: 24V (pulse modulation)
3. Operating current: 300uA (monitoring status) or 1.5mA (alarm status)
4. Work indication: the red indicator will blink in the Monitoring status or remain lit in the alarm status.
5. Weight:about47g
6. Product class: A2
7. External Dimensions: diameter:100mm, Height:56mm(with the base)
8. Wiring method: non-polarity Two-bus system (L1, L2)
9. Operating environment: Indoor, temperature: 10+50; Relative humidity: 95% (402, without Condensation)
10. Coding mode: It can realize electronic coding via coder in Situ. Address codes 1 to 324 are available for selection.
11. Installation height: 8m
12. Protection area: about60m2. for details, see related provisions in GB50116-98Code for Design of Automatic Fire Alarm System.
13.
Matched host machine: fire alarm control panel (such as MN300)