Place of Origin: | China (Mainland) |
---|---|
Brand Name: | MINGRUI |
Model Number: | MRD-BJ/FD |
Quick Details
Specifications
A neutral grounding resistor limits the fault current to a value which is sufficient enough to operate protective relays, yet prevent unwanted fault damage.
Safety enclosure:our resistor assemblies are available with grounded safety enclosures to protect personnel and wildlife from harm. Screened and louvered enclosures are available in a variety of finishes including painted, power coated, mill galvanized, hot-dipped galvanized, aluminum and stainless steel.
Electrical tests
All units are factory tested in accordance with IEEE Standard 32-1972, specifically Section 10.1.4 and 10.3.2. The procedure includes a resistance measurement test to verify that the tolerance is within +10%, and an applied potential test. A copy of the test report is included with each shipped unit.