Place of Origin: | China (Mainland) |
---|---|
Brand Name: | SoCan |
Model Number: | scy5 |
Usage: | Magnetic Sensor |
Theory: | Current Sensor |
Output: | Analog Sensor |
Principle: | Hall effect split core |
Quick Details
Specifications
SCY5 Series Open Loop Split Core Hall Effect Current Sensor
Technical Parameters
Open Loop Current Sensor (Split-core current sensor)
Model: 500A 800A 1000A 1200A 1500A 2000A
Nominal Rms Current (Ipn) : ±500AT ±800AT ±1000AT ±1200AT ±1500AT ±2000AT
Measuring Range (Ip): 2*Ipn
Load resistance Rmax: 10kΩ
Supply Voltage: ±4V or ±5V
Working voltage: DC ±12V~±15V(±5%)
Dynamic Performance Data:
Accuracy @ Ta=25°C: ±1% FS
Linearity @ Ta=25°C: ±1% FS
Withstand voltage: 3kVrms/50Hz/min
Offset Voltage: < ±30mV
Offset temperature characteristics: < ±0.1%/°C
Thermal drift of Vo: < ±1mV/°C (If=0)
Hysteresis offset: < ±25mV (if=F.S. 0<--- --->Nominal RMS Current)
Response time: < 7uS
Current consumption: <±23mA
General Data:
Operating temperature: -20~+80 °C
Storage temperature: -40~+85 °C
Hole inside diameter (mm): 16*64
Instructions
1. SCY5 Series 's up and down can open and close without removing the busbar line, easy to install.
2. Based on open-loop principle, it can measure DC, AC and Pulse current.
3. Square perforation, mainly measure copper conductor current.
4. Features: High accuracy, low power consumption, high liability and strong overload capacity.
Weight and Package:
Net weight 375g
4SETS PER CARTON BOX
Caution: Incorrect wiring may damage the sensor