Place of Origin: | China (Mainland) |
---|---|
Brand Name: | mingrui |
Model Number: | BPZM-MRD |
Quick Details
Specifications
In the electric power system, large capacity transformer is mainly oil immersed power transformer, its stable operation is important to ensure the safe operation of the power system. At present, the nitrogen-injection fire extinguish in device with its exclusive feature of prevention first and combination of fire prevention and fire fighting, has become an important fire control facility for oil immersed power transformer.
BPZM is the newly device which are specially applied for oil immersed transformer.
Working condition:.
Detector, block valve, fire prevention cabinet can be installed outdoor while control panel should be installed indoor. Installation site should be free from violent vibration, impact and corrosive gas
Ambient air temperature
outdoor: -40~60℃
Indoor: 5~30℃
Working power: DC220V/DC110V
Relative humidity:
≤95 (at 20℃±5℃);
≤85 (at 20℃±5℃)
Please specify the following information when ordering
1. the ichnography and contact information of factory of transformer
2. others request please offer when you ordering
Note: Customized products are available
≤50 |
>50, ≤240 |
>240 |
|
Volume of N2 (L) |
40 |
40 |
40 |
No. of N2 Bottle |
1 |
2 |
4 |
Initial Pressure of N2 Bottle (MPa) |
15 |
||
Pressure after depressurization (MPa) |
0.6 |
||
Volume of N2 after Decompression (L) |
1000 |
2000 |
4000 |
Continuous Time of N2 Injection (min) |
31 |
||
Valve Outlet after N2 Injection (L/min) |
32.25 |
64.51 |
101.61 |
Flow Speed of N2 in the bottle (m/s) |
1.095 |
2.19 |
3.45 |
N2 Injection hole quantity |
2 |
4 |
6 |
Flow Speed of Injection Hole (L/min) |
16.13 |
16.13 |
16.94 |
Fire-Extinguishing time(min) |
≤1min |
||
Operation temperature of Temperature Detectors (℃) |
130℃ ±10℃ |
||
Diameter of oil pipe(mm) |
Φ100 |
||
diameter of nitrogen injection pipe(mm) |
Φ25 |
||
Operation time of fast vent valve(s) |
<1s |
||
Operation temperature of fire extinguishing cabinet (℃) |
Ⅰ:-20℃~60℃ Ⅱ:-40℃~60℃(Ⅱalpine region |
||
Weight of fire extinguishing cabinet |
230-240KG |
||
Pressure controller action |
0.06-0.16Mpa(adjustable) |
||
Nominal pressure inner nitrogen gas cylinder: |
13.5MPa(20℃); |
||
Fire extinguishing cabinet Control circuit pressure: |
DC220+5%V, |