Model Number: DKJ-2100,DKJ-3100,DKJ-4100,DKJ-5100
Brand Name: Freya
Place of Origin: China (Mainland)
Inpuit signal: 1-5V or 4-20mA
Feedback signal: 4-20mA
Voltage: 220V,230V
Output torque: 100NM-10000NM
Valve open time: 25s-100s
Motor working system: 50%
Protection grade: IEC14 IP65

Specifications

DKJ-D (DY-J) series electric actuator is a new product of our factory. On the basis of the ordinary DKJ electric actuator, it incepts advanced foreign technology, and adopts new foreign technology, new devices to form this fully electronic product with intelligent functions which is the combination of control circuit and actuator.

DKJ-D (DY-J) electric actuator can receive directly computer DCS or all kinds of regulating units 4~20mA or 1~5V , and control various regulating mechanisms such as damper, valve, baffle, etc. There is no need to install servo amplifier additionally. It can be widely used in electron, metallurgy, oil, chemistry.

DKJ-D (DY-J) series electric actuator has the function of operating manually. It can adjust the actuator on the spot. If plus the DFD type electric actuator, it can realize the " manual-automatic" switchover of        system without disturbance, and remote manual control to the controlled plant.

 

Specifications and types

 

 

 

specifications

output torque Nm

travel time S

weight(kg)

4~20mA

4~20mA

DY-J21T

DKJ-2100D

100

25

30

DY-J31T

DKJ-3100D

250

45

DY-J41T

DKJ-4100D

600

75

DY-J51T

DKJ-5100D

1600

125

DY-J61AT

DKJ-6100AD

2500

40

130

DY-J61T

DKJ-6100D

4000

60

175

DY-J71T

DKJ-7100D

6000

60

230

DY-J81T

DKJ-8100D

10000

100

230

 

Main technical performance

 

1. Input signals: mode II: 0~10 mA, DC; mode III: 4~20 mA, DC

2. Input passages: 3

3. Input channel resistance: mode III: 250Ω, mode II: 200Ω

4. Output thrust: see dynamic parameter

5. Whole travel time: see dynamic parameter

6. Basic error: ±2.5%

7. Dead band: ≤3%

8. Damping characteristic: ≤ a half and three cycles

9. Return difference: 1.5%

10. Voltage of the power supply: 220V(+10%,~15%)  frequency: 50HZ

11. Temperature of the operating environment:

   Actuator: -10~+55°Cor -25~+70°C

Amplifier: 0~+50°C

12.Relative humidity of the operating environment:

Actuator: ≤95%

Amplifier: 10%~70%