Product Main

Quick Details

Model Number: DKZ-4100 ,4200,4300,5400,5500,6600
Brand Name: Frea
Place of Origin: China (Mainland)
Input signal: 4-20mA
Feedback signal: 4-20mA
Load: 4000N,6400N,16000N
Travel distance: 10mm-100mm
Motor working system: 50%
Protection grade: IP55,IP65

Specifications

 Commodity:  DKZ series electric actuator

 

DKZ series electric actuator are the terminal control device of industrial process survey and the control system, changing the system's control signal into angular displacement, linear displacement of output axle, the position of valve and other regulating units. The main purpose is to enable the controlled medium to work well under the regulated system conditions.

The electric actuator is divided into the proportion type and integral type according to the controlling type. The proportion actuator is made up of electric servo amplifier and integral type actuator that can compare systematic control signal with the feedback signal (closed-loop control) of output axis so as to change the travel route and has proportion relations with the output axis signal. The integral actuator consists of servo motor, reducer and position transmitter. Coordinating with motor operator, it can control valve or other regulating units from long distant.

 

 

Specifications and types

 

model 

Thrust output N

Travel

mm

Full treavel time S

DKZ-4100D

4000

10

8

DKZ-4200D

4000

16

12.8

DKZ-4300D

4000 

25

20

DKZ-5400D

6400

40

32

DKZ-5500D

6400 

60

48

DKZ-5600D

16000

100

80

 

 

 

Main technical performance 

 

1. Input signals: mode II: 0~10 mA, DC; mode III: 4~20 mA, DC

2. Input passages: 3

3. Input channel resistance: mode III: 250Ω, mode II: 200Ω

4. Output thrust: see dynamic parameter

5. Whole travel time: see dynamic parameter

6. Basic error: ±2.5%

7. Dead band: ≤3%

8. Damping characteristic: ≤ a half and three cycles

9. Return difference: 1.5%

10. Voltage of the power supply: 220V(+10%,~15%)  frequency: 50HZ

11. Temperature of the operating environment:

   Actuator: -10~+55°Cor -25~+70°C

Amplifier: 0~+50°C

12.Relative humidity of the operating environment:

Actuator: ≤95%

Amplifier: 10%~70%