Insulation Material: PVC
Jacket: PVC
Conductor Material: Copper
Shielding: Braid
Model Number: IA-DJYPVP
Brand Name: shenglong
Place of Origin: China (Mainland)
executive standard: TICW/06-2009

Specifications

 

Blue sheath intrinsic safety shielded computer cable

Application: the cable has low capacity, low inductance, excellent shield property, interference resistance, incombustibility, acid and alkali resistance properties. The structure is designed for intrinsic safety anti-explosion, fit to the bridge laying, install in the cable trench and bury directly. It is used to the distributed system, automated test system which required anti-explosion and the severe service environment and computer control cable which requires high anti-explosion safety property.  

Standard: product up to TICW/06-2009; equivalence up to BS5308; flame retardant up to GB12666-90.

Use terms:

Max working temperature: for PE insulation is 70 Celsius degree; for XLPE insulation is 90 Celsius degree; for low smoke zero halogen POis 70 Celsius degree; for low smoke zero halogen flame retardant XLPO is 90 and 125 Celsius degree; for F46 insulation is 200 Celsius degree; for imported PFA insulation is 260 Celsius degree.

Working voltage: AC rated 300/500kv

Minimum environment temperature:

for PVC sheath, fixed installation is -40 Celsius degree; unfixed installation is -15 Celsius degree.

For PVDF and silicone rubber sheath: fixed installation is -60 Celsius degree; unfixed installation is -25 Celsius degree.

Installation environment temperature: no lower than 0 Celsius degree (high temperature type is no lower than -25 Celsius degree).

Minimum bending radius: 6*overall diameter for unarmored cable; 12*overall diameter for Cu tape shielded or the steel tape armored cable.

Technical index:

performance

unit

index

0.5

0.75

1.0

1.5

2.5

Work capacity(1kz)

PF/M

≤60

≤70

≤80

≤90

Capacity unbalance

PF/M

No more than 1

Distributed inductance

uh/m

No more than 0.6

L/R ratio

uh/Ohm

≤15

≤25

≤35

≤50

Electromagnetic interference induced voltage(disturbing magnetic field400A/M)

MV

No more than 5

Static induced voltage(static voltage 20 kv)

V

No more than 1

Radiation field penetration intensity(disturbing field 200MZ,120db)

db

No more than 66

20 Celsius degree insulation resistance

M ohm/km

No less than 5000(PVDF insulation is no less than 500)

Test voltage

V

2000v 1min

Flame retardant and flame resistance test

Up to GB 12666-90

Cable code name and meaning

Item

Code

Meaning

Flame retardant property

ZR

A, B, C grade

Series code

IA-DJ

Intrinsic safety computer cable(including DCS cable)

Insulation material

Y

PE

YJ

XLPE

WD

Low smoke zero halogen flame retardantPO

F (F46)

FEP

Sheath material

WD

Low smoke zero halogen flame retardantPO

V

PVC

G

Silicone rubber

Shielded material

P

Cu wire braid shielded

P1

Tinned Cu wire shielded

P2

Cu tape wrapped shielded

P3

Al/plastic tape wrapped shielded

Armor material

22

Steel tape armored PVC sheath

32

Steel wire armored PVC sheath

Conductor structure

A

Single conductor

B

7-strand stranded conductor

R

Multi-strand stranded conductor

Specification

Couple no 1-37

Core NO per couple 2-3