Ⅰ.Introduction
DGA2013-1 Power system Dedicated Insulation Oil and
Gas Chromatography Analysis System Manualruns by computer automatic
control, all-keyboard operation andlarge-screen
liquid crystal displayaccording to the
requirements of power system?dissolved gas component determination in
insulation oil (chromatography)? ,and is characterized by high-precision
temperature control, stable and reliable performance, high sensitivity, good
reproducibility and so on.
The analyzer adopts double-pillar parallel shunt
system ,equipped with TCD, double FID and methane conversion oven, and could
achieve total analysis of nine components (H2,O2,N2,CH4,C2H2,C2H4,C2H6,CO,
CO2)of dissolved gas in insulation oil by one time.
The analyzer can be employed
for internal fault detection of power system oil and gas equipments, cooling
medium analysis of hydrogen-cooled generators, impurity analysis of sulfur hexafluoride,
the boiler flue gas analysis, gas analysis and environmental monitoring
analysis. Due to its employment not only for special analysis, but also for
general analysis, the analyzer becomes the most effective gas analytical
instrument in petroleum, chemical engineering, mining and other systems.
1.Main technical specification
1.1Temperature control
① Temperature range
Column chamber: room temperature+15℃—399℃
Vaporizing chamber: room temperature+30℃—399℃
Conversion furnace :room temperature+30℃—399℃
Thermal conductivity detector: room temperature+30℃—399℃
Hydrogen flame detector :room temperature+30℃—399℃
② Temperature control precision: ±0.1℃
1.2 Thermal conductivity detector
① Sensitivity: minimum detectable concentrationof hydrogen≥5μl/L
②Noise: ≤0.05mv
③Drift: ≤0.15mv/30min
1.3 Hydrogen flame detector
①Minimum detectable concentration of hydrocarbon≥5μl/L
②Minimum detectable concentration of CO, CO2≥5μl/L
③Noise: ≤0.05mv
④Drift: ≤0.15mv/30min
1.4Whole machine start-up time: less than 3 hours
2.Main performance characteristics
2.1 Computer-keyboard operation
This realizes five heating zone temperature control, detector control, over-temperature protection, "zero" degree protection, air break protection and other functions, so as to protect the chromatographic column and thermal conductivity rhenium tungsten filament most effectively.
2.2 Large-screen liquid crystal display
It could display a large amount of information intuitively and clearly.
2.3 Advanced chromatography process
Based on only one injection and three-detectors analytical process, the analyzer greatly increases detection sensitivity of hydrocarbon gas. Double hydrogen flame setting also reduces the detection impact caused by the gas content differences.
3.Working conditions
3.1 Normal instrument working conditions
①Environmental condition: 5℃—35℃
② Relative Humidity: ≤80%
③ Power supply: 220V±10% 50Hz±0.5Hz
④ 3KW power provided.
⑤ No strong electromagnetic interference, corrosive gas and strong shock in the
surroundings.
3.2 Gas source
① Air purity: ensure the purity of carrier gas and hydrogen
is more than 99.99%, the air to be used is purified and air generator function in
dust, oil and water removal.
②Output pressure of steel cylinder relief valve: nitrogen
0.35MPa, hydrogen 0.25MPa, air 0.35MPa
③ Please replace steel cylinder timely when output pressure
fell below 2MPa.
3.3 Ground wire
To ensure personal safety and instrument performance, the
instrument must be reliably linked to the land. It is suggested to bury the
ground wire in the soil 1 meter below.