| Temperature range: | -50~1300 centigrade |
|---|---|
| Accuracy: | plus-minus 0.5%F.S. |
| Theory: | Temperature Controller |
| Usage: | Industrial |
| Model Number: | CTM-9 (amanda2tinkosz.com) |
| Brand Name: | Tinko |
| Place of Origin: | China (Mainland) |
| panel size(mm): | 96*96 |
| mount size(mm): | 92*92 |
Quick Details
Specifications
Aplication:
Can be applied together with temperature probe to control temperature of heating or cooling equipment, plastic machinery, oven, etc.; Can also cooperate with other probe used in the need for humidity, pressure, flow, liquid level control.
Specification:
Power Supply: AC85~265V,50/60Hz
Accuracy: ±0.5%F.S.
Input Signal: Thermocouple (K, E, J, N, T, B, S)
RTD (Pt100, Pt1000, Cu50, Cu100)
Current (DC.0~20mA, DC.4~20mA)
Voltage (DC.0~250mV, DC.0~10V)
Resistor (0~80Ω, 0~400Ω)
Control Output: Relay contact, AC250V/3A
SSR Drive (Voltage pulse)
SCR Drive (zero-crossing)
DC.4~20mA, DC.0~10V
Alarm Mode: Absolute, Deviation, Range
Communication: RS485, Tinko Protocol
Aux Output: Micro-printer drive, DC24V feedback
Panel Size (mm): 48*48,72*72,48*96,96*96,160*80
Single-loop Controller:
l. Fuzzy PID, control fast & smooth
2. Can choose input signal preprocessing, such as root operation
3. PV bias, PID self-tuning, manual control functions
4. Thermocouple/RTD break, inverse or short alarm
Double-loop Controller:
1. Input signals can be different
2. Double-loop control separately
3. Alarm outputs & signal inputs combination free
4. PV bias, PID self-tuning, manual control functions
5. Thermocouple/RTD break, inverse or short alarm
Programmable Controller:
1. Max. 12sets application period (target, heating & hold time)
2. Starting point can be chosen
3. Process can be paused
4. Repeat times can be set
5. End alarm can be set
Model and Suffix Code
|
CTM- □ □ □□□ -□□ -□□□□ -□□ -□ -□□ ⑴ ⑵ ⑶ ⑷ ⑸ ⑹ ⑺ ⑻⑼ |
Box (1)-Front panel size
|
Code |
Size(W*H) |
|
1 |
160*80mm |
|
4 |
48*48mm |
|
5 |
48*96mm |
|
6 |
96*48mm |
|
7 |
72*72mm |
|
9 |
96*96mm |
Box(2)-Control method
|
Code |
Descriptions |
|
Z |
Display & none alarm |
|
P |
Alarm mode |
|
F |
PID auto-tuning |
|
M |
Programmable PID |
Box(3)-Input type
|
Code |
Descriptions |
|
K01 |
K(0~1300)℃ |
|
K02 |
K(0~400)℃ |
|
E01 |
E(0~1000)℃ |
|
J01 |
J(0~1000)℃ |
|
N01 |
N(0~1300)℃ |
|
T01 |
T(0~400)℃ |
|
S01 |
S(0℃~1600)℃ |
|
B01 |
B(0℃~1800)℃ |
|
R01 |
R(0~1700)℃ |
|
P01 |
Pt100 (-100~200)℃ |
|
P02 |
Pt100 (-200~600)℃ |
|
C01 |
Cu50 (-50~150)℃ |
|
W01 |
W 5 / W 2 |
|
201 |
0~80Ω |
|
202 |
0~400Ω |
|
401 |
0~5V |
|
402 |
0~10V |
|
501 |
0~50mV |
|
502 |
0~250 mV |
|
701 |
0~20 mA |
|
702 |
0~10mA |
|
801 |
4~20mA |
|
901 |
others |
Box(4)-Output type
|
Code |
Descriptions |
|
N |
None |
|
M |
Relay contact output |
|
V |
SSR drive output(voltage pulse) |
|
G |
SCR drive(zero crossing) |
|
8 |
4~20mA |
|
9 |
0~10VDC |
Box(5)-Alarm output
|
Code |
Descriptions |
|
N |
No alarm |
|
M |
Relay contact output |
Box(6)-Transmission output
|
Code
|
Descriptions |
|
8 |
4~20mADC output |
|
9 |
0~10VDC output |
|
N |
None output |
Box(7)-Power feedback output
|
Code |
Descriptions |
|
N |
No output |
|
V4 |
24VDC output |
Box(8)-Data output
|
Code |
Descriptions |
|
N |
No data output |
|
C |
RS485 output |
Box(9)-Mircro-printer drive output
|
Code |
Descriptions |
|
N |
None |
|
Z |
TTL signal output |