Certification: | CE, CCC, SGS, ROHS,ISO |
---|---|
Application: | Refrigeration Parts |
Type: | Condenser |
Model Number: | LB-C-01 |
Brand Name: | Bitzer LB |
Place of Origin: | China (Mainland) |
Condensation Forms:: | Water/Air Cooled |
Voltage:: | 380V/3p/50Hz or 220V/1p/50Hz |
Refrigerant:: | Freon,R22 (R404A for Selection) |
Compressor Horse Power:: | 5~ 30HP |
HS Code:: | 8418619000 |
Quick Details
Specifications
Specifications:
All models Bitzer Condensing Unit :
1. from 5~ 30hp
2. single stage,two stage
3. R22,R407C,R134A,R507a/R404A
4. Made in Germany
Bitzer Condensing Unit
Features:
1. With 100% new Bitzer semi-hermetic, two stage compressor
2. With world famous refrigerant components
3. With mid stage design to greatly improve EER value
4. With lower evaporate temp. Min. evaporate temp. can be -65℃ when system with R404A refrigerant
Key components:
Other components:
Two-stage compressor , heater , eliminator, Oil separator , Condenser, Receiver filter , sight glasses, sub cooler, Gas separator , pressure controller, Oil pressure difference controller.
Technical Datas:
1. Bitzer Two-stage Condensing Unit (Air-cooled)
Unit Model |
Compre- ssor Model |
Unit Power |
Refri Capacity |
Piping Size |
Dimensions(mm) |
Installation Size(mm) |
||||
KW |
W |
Air |
Liquid |
L |
W |
H |
a |
b |
||
S4T5.2 |
S4T5.2 |
3.6 |
2820 |
?28 |
? 16 |
1050 |
880 |
580 |
800 |
835 |
S4N8.2 |
S4N8.2 |
5.0 |
3990 |
? 28 |
? 16 |
1050 |
880 |
580 |
800 |
835 |
S4G12.2 |
S4G12.2 |
7.5 |
6090 |
? 35 |
? 22 |
1050 |
880 |
700 |
800 |
835 |
S6J16.2 |
S6J16.2 |
10.5 |
9540 |
? 42 |
? 22 |
1050 |
1000 |
750 |
800 |
955 |
S6H20.2 |
S6H20.2 |
12 |
11060 |
? 42 |
? 22 |
1050 |
1000 |
750 |
800 |
955 |
S6G25.2 |
S6G25.2 |
14.5 |
12700 |
? 42 |
? 22 |
1050 |
1000 |
750 |
800 |
955 |
S6F30.2 |
S6F30.2 |
17 |
15200 |
? 42 |
? 22 |
1050 |
1000 |
750 |
800 |
955 |
PS:1,Refrigerating Capacity and Unit Power test in condition:-40℃/40℃(withno intercooler).
2. Bitzer Two-stage Condensing Unit (Water-cooled)
Unit Model |
Compre- ssor Model |
Unit Power |
Refri Capacity |
Water flow capacity |
Piping Size |
Dimensions(mm) |
Installation Size(mm) |
||||
KW |
W |
M3/h |
Air |
Liquid |
L |
W |
H |
a |
b |
||
S4T5.2 |
4ST-5.2 |
3.02 |
3120 |
1.4 |
? 28 |
? 22 |
1050 |
920 |
580 |
800 |
875 |
S4N8.2 |
S4N-8.2 |
4.3 |
4490 |
2 |
? 28 |
? 22 |
1050 |
550 |
790 |
710 |
460 |
S4G12.2 |
S4G-12.2 |
6.43 |
6790 |
3 |
? 35 |
? 28 |
1080 |
550 |
790 |
800 |
460 |
S6J16.2 |
S6J-16.2 |
8.86 |
10460 |
4.3 |
? 42 |
? 28 |
1250 |
650 |
860 |
850 |
555 |
S6H20.2 |
S6H-20.2 |
10.3 |
12120 |
5 |
? 42 |
? 28 |
1290 |
650 |
910 |
850 |
555 |
S6G25.2 |
S6G-25.2 |
11.8 |
13920 |
5.7 |
? 42 |
? 28 |
1290 |
650 |
910 |
850 |
555 |
S6F30.2 |
S6F-30.2 |
14.1 |
16650 |
6.8 |
? 42 |
? 28 |
1290 |
650 |
910 |
850 |
555 |
PS:1,Refrigerating Capacity and Unit Power test in condition:-40℃/40℃
(with no inter-cooler).
Packaging & Delivery
Packaging Detail: By Sea:Export wooden package,with refrigerant oil By Air :Full-sealed wooden package, without refrigerant oil.
Delivery Detail: 3-5days