Product Main

Quick Details

Rated Current: 360A
Rated Voltage: 380V/220V
Rated Power: 200KW
Frequency: 50HZ
Speed: 1500RMP
Output Type: AC Three Phase
Model Number: JGV200GF
Brand Name: FD
Place of Origin: China (Mainland)
Engine Model: TAD734GE
Configuration: 4 cycle , 6 cylinders in line
Displacement: 7.15 L
Fuel Consumption at 100% Load: 204g/kw.h
Alternator Model: UCI274K
Exciter type: Brushless, Self-excited

Specifications

 

Criterion

 

General feature


Coupled with Volvo diesel engine and Stamford

Or Marathon alternator
24V DC start motor and storage battery
Brushless, Self-excited, IP23, insulation class H alternator

40 radiator as standard, 50 is optional

Key start panel control system as standard, digital auto-start panel is optional

Optional open type or silent type

All generator sets are gone through rigorous testing before being released to the market place, including 50% load, 75% load, 100% load , 110% load and all protection function (overspeed stop, high water temperature, low oil pressure, battery charging fail, emergency stop)
 

Genset Main Technical Data

 

Generator Model

JGV200GF

Prime power

200KW

Standby power

220KW

Voltage

380V/220V

Frequency

50HZ/1500 rpm

Power factor

0.8(lag)

Governor type

Electric


 

Prime Power : Prime power is available for an unlimited number of annual hours in variable load application, in accordance with GB/T2820-97; A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.

Standby Power Rating : The standby power rating is applicable for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.

Reliable Performance


Voltage regulation

Voltage regulation maintained within ±0.5% as follow:

Power factor Between 0.81.0 lag

From no load to full load, any steady load

Speed droop variation under 4.5%
 

Frequency/Speed undulation

Change load from 0-100%, Frequency/Speed Droop Ratio within 5%

Load from 25-100%, any steady load Frequency/Speed undulation within 0.25%

Effect factor of telecom

Telephone Influence Factor (TIF) : Less than 50

                           THF : Less than 2%
 

ISO8528, GB/T2820

EN12601:2001, EN60034-22:1997, EN60204-1:2006

ISO9001:2008 Quality Control System sion and Weight

  

Volvo Diesel Engine

Technical Data

Engine Model

TAD734GE

Configuration

4 cycle , 6 cylinders in line

Aspiration

Turbochargerd

Bore×Stroke

108x130 mm

Rated speed

1500rpm

Displacement

7.15 L

Compression ratio

17.0:1

Prime Power

217KW

Speed Governor

Electronic

Cooling System

water-cooled

Speed Stability (%)

≤5%

Fuel Consumption at 100% Load

204g/kw.h

Starter Motor

24V,


Alternator
 

Brand

Stamford

Alternator Model

UCI274K

Capacity

200KW

Voltage

220/380V

Frequency & Speed

50HZ/1500RPM

Exciter type

Brushless, Self-excited

Power factor

0.8

Voltage Adjust range

≥5%

Voltage Regulation NL-FL

≤±0.5%

Insulation Grade

H

Protection Grade

IP23


 Control system

1. Standard: HGM180HC Key Start

Providing the standard functions as follows:

(Also can be made according to the customers' special requirements)

Start/Stop controller

Ampere meter

Voltmeter and selector switch

Frequency meter/ Water temperature gauge/ Oil pressure gauge/ Hour counter/ Battery voltage meter

Emergency stop pushbutton

Alarm System: Over speed, High Engine Temperature

Low Oil Pressure, Charge Fail

Protection System: Over speed, High Engine Temperature, Low Oil Pressure, Emergency Stop. And the other protection function pre-setting

Digital Auto-start Generator controller integrating digital, intelligent and network techniques is used for automatic control system of diesel generator. It can carry out functions including automatic start/stop, data measure and alarming. Optionally assembled with the ATS, it can carry out auto-switching betweeFunction

Automatic Start/Stop

3 start attempts failure and Automatic Crank Disconnect               

Parameters display (V/A/Hz/Hour)

Engine monitoring and protection

Charge alternator exciting and Charge alternator fail alarm

Running hour counting

Settings can be adjustable via key buttons on front panel

. Option: Smartgen HGM6110 Digital Auto Start

3. Option: Smartgen HGM6120 Digital Auto Start

   (Option assembled with the ATS)

4. Option: Deep Sea DSE5210 Digital Auto Start      

5. Option: Deep Sea DSE5220 Digital Auto Start

   (Option assembled with the ATS) 

rion

rit 

ISO8528, GB/T2820

EN12601:2001, EN60034-22:1997, EN60204-1:2006

ISO9001:2008 Quality Control System

erion