0.6-1(1.2)KV Heat Shrink Termination

Applications:
Low voltage heat shrinkable terminations for 0.6/1.0(1.2)kV.

Features:
Histe Low Voltage Heat Shrinkable Terminations
Termination kits for polymeric insulated cables with amore/concentric neutral, with mechanical/bolted lugs.

Introduction
0.6/1kV Heat shrinkable technology is one of the worlds most simple and cost effective jointing system. When connecting 1kV power cables, Histe heat shrink tubing will insulate a variety of cables with XLPE, PVC, and MI/MIND paper insulation. All Histe kits are designed to be compact and range taking resulting in lower cost and reduced stock quantities. Histe's advanced polymer technology ensures high performing standards of both tubing and the adhesive. Performance and long term reliability are guaranteed, with excellent weathering resistance.

0.6/1kV Heat Shrinkable Low Voltage Cable Accessories Technical Data
Test sequence

Item

Requirements acc. to EN50393

Results

Remarks

EN50393

1

Implusee withstand voltage test

No breakdown shall occur at 10 positive and 10 negative impluses of 20kV

No breakdown shall occur at 10 positive and 10 negative impluses of 20kV

PASS

2

AC withstand voltage test(in air and abbient temperature)

4kV, 1min,No breakdown

4kV, 1min,No breakdown

PASS

3

Insulation resistance(in air and ambient temperature)

≥50MΩ

≥50MΩ

PASS

4

Impact test(in air and ambient temperature)

4kg wedge dropped from a height of 1000mm

4kg wedge dropped from a height of 1000mm

PASS

5

AC withstand voltage test immersed in the water of with a height of 1000mm

4kV,1min, No breakdown

4kV,1min, No breakdown

PASS

6

Heating cycle test(immersed in the water of with a height of 1000mm)

Heat the conductor to 95℃--100℃ , 60 times in the water, No breakdown

Heat the conductor to 95℃--100℃ , 60 times in the water, No breakdown


Table of specification of 1kV Heat Shrinkable Cable Accessories Technical Data
Product Code Name For Cable
Mm2 Product
Code Name For Cable
Mm2
NRSY01-1/0 1-coresterminations 10-16 JRSY01-1/0 1-coresjoints 10-16
NRSY01-1/1 1-coresterminations 25-50 JRSY01-1/1 1-coresjoints 25-50
NRSY01-1/2 1-coresterminations 70-120 JRSY01-1/2 1-coresjoints 70-120
NRSY01-1/3 1-coresterminations 150-240 JRSY01-1/3 1-coresjoints 150-240
NRSY01-1/4 1-coresterminations 300-400 JRSY01-1/4 1-coresjoints 300-400
NRSY01-2/0 2-coresterminations 10-16 JRSY01-2/0 2-coresjoints 10-16
NRSY01-2/1 2-coresterminations 25-50 JRSY01-2/1 2-coresjoints 25-50
NRSY01-2/2 2-coresterminations 70-120 JRSY01-2/2 2-coresjoints 70-120
NRSY01-2/3 2-coresterminations 150-240 JRSY01-2/3 2-coresjoints 150-240
NRSY01-2/4 2-coresterminations 300-400 JRSY01-2/4 2-coresjoints 300-400
NRSY01-3/0 3-coresterminations 10-16 JRSY01-3/0 3-coresjoints 10-16
NRSY01-3/1 3-coresterminations 25-50 JRSY01-3/1 3-coresjoints 25-50
NRSY01-3/2 3-coresterminations 70-120 JRSY01-3/2 3-coresjoints 70-120
NRSY01-3/3 3-coresterminations 150-240 JRSY01-3/3 3-coresjoints 150-240
NRSY01-3/4 3-coresterminations 300-400 JRSY01-3/4 3-coresjoints 300-400
NRSY01-4/0 4-coresterminations 10-16 JRSY01-4/0 4-coresjoints 10-16
NRSY01-4/1 4-coresterminations 25-50 JRSY01-4/1 4-coresjoints 25-50
NRSY01-4/2 4-coresterminations 70-120 JRSY01-4/2 4-coresjoints 70-120
NRSY01-4/3 4-coresterminations 150-240 JRSY01-4/3 4-coresjoints 150-240
NRSY01-4/4 4-coresterminations 300-400 JRSY01-4/4 4-coresjoints 300-400
NRSY01-5/0 5-coresterminations 10-16 JRSY01-5/0 5-coresjoints 10-16
NRSY01-5/1 5-coresterminations 25-50 JRSY01-5/1 5-coresjoints 25-50
NRSY01-5/2 5-coresterminations 70-120 JRSY01-5/2 5-coresjoints 70-120
NRSY01-5/3 5-coresterminations 150-240 JRSY01-5/3 5-coresjoints 150-240
NRSY01-5/4 5-coresterminations 300-400 JRSY01-5/4 5-coresjoints 300-400