Rated Voltage: | 380VAC |
---|---|
Rated Power: | 500KW |
Frequency: | 50HZ/60HZ |
Output Type: | AC Three Phase |
Model Number: | AC380-500 |
Brand Name: | Triumph load |
Place of Origin: | China (Mainland) |
Quick Details
Specifications
Portable Indoor Load Bank offers the most robust, high-capacity designs in the industry. It is setting the standard with intelligent operator controls, safety indication layouts, adjustable load step resolution, and lightweight designs. The Portable Indoor Load Bank is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems.
AC380-500kW Automatic Load Bank |
|
Rating Voltage/Frequency |
500Kw at 380VAC, 3 phase 4 wire, 50 Hz, 220V-Ph |
Max Load Power |
Resistive load: 510kW |
Load Steps |
11steps, Resistive load: 1KW,2KW,2KW,5KW,10KW,20kW, 20kW,50kW,100kW, 100kW,200kW min load step: 1 kW |
PF(Power Factor) |
1 |
Load Accuracy (each step) |
±5% |
Load Accuracy (overall) |
3% |
Display Precision |
0.5 grade |
Control Power |
380VAC, 3 phase 4 wire, 50 Hz, phase voltage220V |
Wire Connection |
Load power supply input-" Y" connection Control power supply input- |
Insulation |
F |
Duty cyle |
Continuous |
Cooling |
Fan forced cooling, horizontal inlet air and vertical outlet cooling |
Casing Color |
Grey(RAL7035) |
Dimensions |
1460 mm*1980mm*1800mm(length*wide*high) |
Weight |
About 750kgs |
Operating Environment Parameter |
|
Temperature |
-10℃~+50℃ |
Relative Humidity |
≤95% |
Altitude |
≤2500 meter |
Brands of Main Components |
|
Contactor |
Schneider |
Fuse |
DELIXI |
Alloy Resistance |
(self-developed) |