Product Main

Specifications

S1-1 1kV Bus Bar Insulation Heat Shrink Tube 
Features
      Flame retardant thin wall cross-linked polyolefin              Operating temperature: -40~105 
      Bus bar insulation and protection              Shrink temperature: 125 
      Reduces bus bar clearance requirement               Shrink ratio: 2:1 & 2.5:1 &  3:1
      Halogen free, RoHS compliant               Voltage class: 1KV 
      Protects against short circuit and electrical leakage caused by small animals
Approvals
UL approval  File No. 341796
Technical Data
Property Test method           Values          
Physical Tensile strength ASTM D2671    14 MPa
Breakdown elongation ASTM D2671 ≥400%
Aging (136/168hrs)  Tensile strength ASTM D2671    12 MPa
Breakdown elongation ASTM D2671  300%
Resistance to selected fluids  Tensile strength IEC 60684-2   8MPa
 (23/168hrs)                         Breakdown elongation IEC 60684-2   250%
Density  ASTM D2671 1.15~1.25
Thermal endurance  IEC 216 125 
Water absorption (23/336hrs) ASTM D570     1.0%
Low temperature flexibility  (-40℃/4hrs) ASTM D2671 No cracking
Heat shock (250℃/4hrs) ASTM D2671 No drop, No flow  
Holdig air test  more than 3  After shrink, no air gap
bendings on bus bar  between H.S.T. and bus bar 
Cutting test (130/168hrs) Raychem method 5mm Length cutting along longitudinal, no cracking 
Halogen free  IEC 61249-2-21 Cl : 900ppm max.Br : 900ppm max.
Total(Cl + Br):1500ppm max.
Electrical Volume resistivity ASTM D2671 ≥10^13 Ω.cm
Dielectric strength(in insulation oil) ASTM D2671    ≥18 KV/mm
Chemical  Flammability ASTM D2863 OI≥ 27
Smoke index  IEC 61034 ≤ 120
Copper corrosion(158℃/168hrs) IEC 60684-3 Pass

Dimensions                                                                            2.5:1
Reference As supplied(mm) After recovered(mm) Standard length
UPM S1-1 ID min. ID max. WT nom. m/spool
15/6 15 6 1.5 30 
30/12 30 12 1.5 30 
50/20 50 20 1.5 30 
75/30 75 30 1.5 30 
100/40 100 40 1.5 30 
120/50 120 50 1.5 30 
150/50 150 50 1.5 30 
175/70 175 70 1.5 30 
3:1
Reference As supplied(mm) After recovered(mm) Standard length
UPM S1-1 ID min. ID max. WT nom. m/spool
30/10 30 10 1.8 30 
75/25 75 25 2.0 30 
100/33 100 33 2.2 30 
150/50 150 50 2.2 30 
180/70 180 70 2.3 30 
Product selection
Bus bar size (mm) Single layer bus bar  Two layers bus bar
20×3,25×3 Φ30/10 Φ30/10
30×3,30×4 Φ30/10 Φ30/10
30×10,40×4 Φ75/25 Φ75/25
40×10,50×5,50×6 Φ75/25 Φ75/25
50×8,50×10,60×6,60×8 Φ75/25 Φ75/25
60×10,80×6,80×8,80×10 Φ100/33 Φ100/33
100×8,100×10,100×12 Φ150/50 Φ150/50
100×15,120×10,120×12,120×15 Φ150/50 Φ180/70
150×12,150×15 Φ180/70 Φ180/70


Shrink ratio: 2: 1
Dimensions
Reference As supplied(mm) After recovered(mm) Standard length
UPM SS1-1 ID min. ID max. WT nom. m/spool
25/12 25 12 0.8 50
30/15 30 15 0.8 50 
40/20 40 20 0.9 50 
50/25 50 25 0.9 25 
60/30 60 30 1 25 
70/35 70 35 1.1 25 
80/40 80 40 1.2 25 
90/45 90 45 1.3 25 
100/50 100 50 1.3 25 
120/60 120 60 1.3 25 
150/75 150 75 1.5 25 
180/90 180 90 1.5 25 
Product selection
Bus bar size (mm) Single layer bus bar  Two layers bus bar
20×3,25×3 Φ25/12 Φ30/15
30×3,30×4 Φ30/15 Φ40/20
30×10,40×4 Φ40/20 Φ50/25
40×10,50×5,50×6 Φ50/25 Φ60/30(Φ70/35)
50×8,50×10,60×6,60×8 Φ60/30 (Φ70/35)    Φ80/40
60×10,80×6,80×8,80×10 Φ80/40    Φ100/50(Φ120/60)
100×8,100×10,100×12 Φ100/50(Φ120/60)     Φ120/60
100×15,120×10,120×12,120×15 Φ120/60      Φ150/75
150×12,150×15 Φ150/75      Φ180/90


Typical application
      Suitable for insulation and protection of bus bar against  accidental flashover up to 1 KV
      Ideal for using in switchgears cabinets where space is limited and air spacing between bus
       bars need to be kept at minimal
Ordering 
     Standard color : Black,Green
     Standard packaging on spools.
     Please specify specification, color, quantity when ordering
Cross reference
Raychem/ Tyco : LVIT