Product Main

Specifications

S1(n)-10 Halogen Free Bus Bar Insulation Heat Shrink Tube 
Features
      Medium wall cross-linked polyolefin               Operating temperature: -40~105 ℃
      Bus bar insulation and protection              Shrink temperature: 125 
      Reduces bus bar clearance requirement               Shrink ratio: 2.5:1
      Halogen free, RoHS compliant               Voltage class: 6~24KV
      Protects against short circuit and electrical leakage caused by small animals
Technical Data
Property Test method           Values          
Physical Tensile strength ASTM D2671    14 MPa
Breakdown elongation ASTM D2671   500%
 Aging  (136/168hrs)                Tensile strength ASTM D2671    12 MPa
Breakdown elongation ASTM D2671  ≥400%
Long term aging          
 (120/3000hrs)         Breakdown elongation IEC 60684-2   ≥175%
Resistance to selected fluids  Tensile strength IEC 60684-2    8MPa
 (23℃/168hrs)             Breakdown elongation IEC 60684-2    250%
Density  ASTM D2671 0.95~1.05
Thermal endurance  IEC 216 105 
Water absorption (23/336hrs) ASTM D570     0.2%
Low temperature flexibility           (-40℃/4hrs) ASTM D2671 No cracking
Heat shock (200℃/4hrs) ASTM D2671 No drop, No flow,No cracking  
Holdig air test  more than 3  After shrink, no air gap
bendings on bus bar  between H.S.T. and bus bar 
Cutting test (110/168hrs) Raychem method 5mm Length cutting along longitudinal, no cracking 
Halogen free  IEC 61249-2-21 Cl:900ppmmax.Br: 900ppmmax.
Total(Cl + Br):1500ppm max.
Electrical Volume resistivity ASTM D2671 ≥1012 Ω.cm
Tracking and erosion resistance ASTM D2303 After 1h at 2.5kV
 or 1h at 2.75kV no tracking
Dielectric strength(in insulation oil) ASTM D2671    ≥16 KV/mm
Chemical  Color fastness to light IEC 60684-3 Compare between exposed and unexposed parts the color
 does not change
Copper corrosion(158℃/168hrs) IEC 60684-3 Pass

Dimensions
Reference As supplied(mm) After recovered(mm) Standard length
UPM S1(n)-10 ID min. ID max. WT nom. m/spool
25/10 25 10 2.50 25 
30/12 30 12 2.65 20 
40/16 40 16 2.65 20 
50/20 50 20 2.65 20 
65/25 65 25 2.85 20 
75/30 75 30 2.85 20 
85/35 85 35 2.85 20 
100/40 100 40 2.85 20 
120/50 120 50 2.85 20 
150/60 150 60 2.90 20 
175/75 175 75 2.90 20 
Product selection
Bus bar size (mm) Single layer bus bar  Two layers bus bar
20×3,25×3 Φ25/10 Φ30/12
30×3,30×4 Φ30/12 Φ40/16
30×10,40×4 Φ40/16 Φ50/20
40×10,50×5,50×6 Φ50/20 Φ65/25 (Φ75/30)
50×8,50×10,60×6,60×8 Φ65/25 (Φ75/30)    Φ75/30(Φ85/35)
60×10,80×6,80×8,80×10 Φ75/30(Φ85/35)    Φ100/40(Φ120/50)
100×8,100×10,100×12 Φ100/40(Φ120/50)     Φ120/50
100×15,120×10,120×12,120×15 Φ120/50      Φ150/60
150×12,150×15 Φ150/60      Φ175/75
ID=Internal Diameter WT=wall thickness
Typical application
      Suitable for insulation and protection of bus bar against  accidental flashover up to 24 KV
      Ideal for using in switchgears cabinets where space is limited and air spacing between bus
       bars need to be kept at minimal
Ordering 
     Standard color : Red
     Standard packaging on spools.
     Please specify specification, quantity when ordering
Cross reference
Raychem/ Tyco : BPTM