1. Application
DZ30LE series is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V, used as electron shock protection. It can protect circuit form overload and short circuit. This product has advantages of small volume, high breaking capacity, live and zero wire are cut off at the same time, also protecting person from electric shock when the live wire connected opposite. It conforms with the standards of IEC61009.
2. Applicable conducting wire
Rated current(A) |
Nominal cross section of wire mm2 |
In ≤ 6 |
1 |
6< In ≤ 13 |
1.5 |
13 < In ≤ 20 |
2.5 |
20 < In ≤ 25 |
4 |
25 < In ≤ 32 |
6 |
40< In ≤ 50 |
10 |
50 < In ≤ 63 |
16 |
3. Residual current breaking time & over-current protection property
In (A) |
In (A) |
Breaking time(s) when equals to rating following |
||||
In |
2In |
5In |
5,10,20,50,100,200,500a(A) |
Itb |
||
6-32 |
0.03 |
0.1 |
0.06 |
0.04 |
0.04 |
0.04 |