Output: | 4-20mA |
---|---|
Power Supply: | +/-21.6-32V DC |
Stability: | +/-0.1% of URL per 12 months |
Vibration Effects: | +/-0.1% of URL |
Ambient temperature effects: | 28 |
Quick Details
Specifications
YOKOGAWA EJA510A Absolute and Gauge Pressure Transmitter
Introduction:
EJA510A and EJA530A can be used to measure liquid, gas, or steam pressure. Both output a 4 to 20 mA DC signal corresponding to the measured pressure,and also feature remote setup and monitoring through communications with the BRAIN? terminal and CENTUM CS? or μXL? or HART? 275 host.
Specification:
EJA510A / EJA530A Direct Mount Type Absolute Pressure and Gauge Pressure Transmitter (Measurement values below are in absolute for EJA510A) | |||||
A Capsule | B Capsule | C Capsule | D Capsule | ||
Range | 0 to 200 kPa (0 to 29 psi) | 0 to 2 MPa (0 to 290 psi) | 0 to 10 MPa (0 to 1450 psi) | 0 to 50 MPa (0 to 7200 psi) | |
Span | 10 to 200 kPa (1.45 to 29 psi) | 0.1 to 2 MPa (14.5 to 290 psi) | 0.5 to 10 MPa (72.5 to 1450 psi) | 5 to 50 MPa (720 to 7200 psi) | |
Accuracy | ±0.2% | ±0.2% | ±0.2% | ±0.2% | |
Degrees of protection | IP67, NEMA 4X, and JIS C0920 immersion proof | ||||
Certificates | FM, CENELEC ATEX, CSA, IECEx | ||||
Output | 4 to 20 mA DC or FOUNDATION? fieldbus or PROFIBUS PA 2-wire system with digital communication | ||||
Supply voltage | BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model) | ||||
Ambient temperature | -40 to 85 deg C (-40 to 185 deg F) (general use type) -30 to 80 deg C (-22 to 176 deg F) (with integral indicator) | ||||
Process temperature | -40 to 120 deg C (-40 to 248 deg F) (general use type) | ||||
Maximum overpressure | 4 MPa (580 psi) | 4 MPa (580 psi) | 20 MPa (2900 psi) | 60 MPa (8500 psi) | |
Mounting | Direct Mounting/2-inch pipe mounting | ||||
Wetted parts material | Capsule | Hastelloy C-276 | |||
Process connection | SUS316L, Hastelloy C-276 | ||||
Housing | Cast aluminum |