Rated Current: | 2804A |
---|---|
Rated Voltage: | 3kV-11kV |
Rated Power: | 1500kW |
Frequency: | 50Hz |
Speed: | 1500rpm |
Output Type: | AC Three Phase |
Model Number: | HGM1875HV |
Brand Name: | Googol |
Place of Origin: | China (Mainland) |
Engine: | Googol QTA3240G6 |
Akternator: | Marathon MXH-1620-4 |
Controller: | Deep Sea |
Application Area: | Industry project, hospital, hotel, etc |
Optional: | ATS, Silent Canopy, Water&Oil heater, etc |
Certificates: | CE, ISO, SGS, TUV, etc |
Warranty: | 1 year or 1000 working hours |
Quick Details
Specifications
Engine Datasheet :
Engine Model | QTA3240-G6 /QTA53-EG6 | |
Speed | rpm | 1500 |
Frequency | Hz | 50 |
Rating Output | ||
Standby Output (LTP) | kW | 1802 |
Prime Output (PRP) | kW | 1644 |
Engine Continuous Power (COP) | kW | 1486 |
Typical Generation Prime Output | kVA | 1875 |
Typical Generation Prime Output | kW | 1500 |
Typical Alternator Efficiency | ≥ | 95.0% |
Voltage of Genset | V | 480 |
MECC alte Generator's Model | ECO46-1.5S/4 | |
MARATHON Generator's Model | MX-1350-4 | |
Basic Performance Datasheet | ||
Aspiration Type | Turbocharger, air-water aftercooler | |
Injection Type | Direct Injection | |
Configuration | Vee | |
No. of Cylinders | 12 | |
Displacement | l | 53.1 |
Bore | mm | 170 |
Stroke | mm | 195 |
Compression Ratio | 13.5:1 | |
Fuel System | ||
Governor Type | Electrical | |
Engine Output at genset prime output | kW | 1644 |
Fuel Consumption at 75% of genset prime output | l/h | 299.09 |
Fuel Consumption at 100% ofgenset prime output | l/h | 394.84 |
Lowest Fuel Consumption Ratio | g/kW.hr | 200.55 |
Intake & Exhaust System(On Standby Output) | ||
Combustion Air Consumption | m3/min | 176.67 |
Max. Intake Restriction | KPa | 2 |
Exhaust Temperature (Before Turbo) | °C | 600 |
Exhaust Temperature (After Turbo) | °C | 480 |
Electrical System | ||
Charging Alternator Voltage | V | 28 |
Charging Alternator Capacity | A | 55 |
Starting Voltage | V | 24 |
Starting Motor Capacity | kW | 13 |
Minimum Battery Capacity | Ah | 4*200 |
Engine Dimension | ||
Length | mm | 3096 |
Width | mm | 1459 |
Height | mm | 1820 |
Engine Dry Weight w/o Cooling System | kg | 5100 |
Performance Feature
Engine and alternator shall be mounted on a same frame steel skid.
Built-in damper for anti-vibration.
World most famous brand diesel engine.
World famous brand AC alternator.
Advanced and reliable control module
Full range protection function and alarm shutdown feature.
Alternator Feature
Brush-less, 4 poles, rotation magnet.
IP21-23(NEMA1) enclosure is standard for all industrial alternators.
The insulation system is Class H
Simple installation and maintenance, with easy access to terminals, rotating diodes and coupling bolts.
Wide range of flange adaptors and single bearing disc coupling.
Standard 2/3 pitch windings avoid excessive neutral currents
AVR auto voltage regulator, auto exciter, auto adjustment
Standard Accessory
Common steel base frame, Damper, Exhaust silencer, Flexible pipe, Battery and connecting wires, Operation manual and document.
Optional Accessory
Engine coolant and oil heater, Alternator space heater, Cooling for heat exchanger, Control system with RS232/485 communication interface, Battery charger by main supply, Fuel-water separator, Daily fuel tank, ATS & paralleling system, and Moving Trailer.
Silent Canopy Description
Standard Accessory:
Steel Weatherproof Canopy
Built In Fuel Tank For 8 Hours Running
Built In Control Panel
Built In Start Battery
Power Output Rapid Insert
Windows for Looking
Air Louver for Intake & Exhaust
Exhaust Gas Silencer
Soundproof Type
Quality Warranty Period:
All equipment is guaranteed for a period of 1000 hours running or 12 months from the date when the generator set has been delivered from the factory.
ATS SYSTEM
For emergency power usage in building, Auto transfer switch (ATS) is essential. ATS can automatic transfer load from Mains power supplying to Emergency power. In normal, when the Main power supplying failure or voltage drop below 80% of normal voltage, ATS will auto start Emergency generator set after a preset time of 0-10 sec (adjustable according to the users). Once generator reach at rated speed, the ATS will transfer the load to emergency generator sets automatically