Dimensions: | 96 x 96 x 12.8 |
---|---|
Operating Temperature: | -5 to +50 celsius degree |
Measuring Voltage Range: | 0-400V |
Measuring Current Range: | 0-6A |
Model Number: | FU2200A |
Brand Name: | GFUVE |
Place of Origin: | China (Mainland) |
Quick Details
Specifications
INTRODUCTION:
FU2200A digital Ethernet power meter with data logger is a three-phase multifunction power and energy meter manufactured
by GFUVE. It provides excellent value for monitoring power and energy management systems. It may be used as data
gathering devices for intelligent power distribution or plant automation systems. All monitored data is available via a standard
digital RS485 communication port, which is based on the Modbus RTU protocol.FU2200A Ethernet power meter has the PC
software and the data logger function, which can set by end users from 1min to 60min intervals to record. You can read the
data through a PC. Also, you can share the data in the Internet LAN. By the way, it can measure the harmonics. Back of
power meter FU2200A with Ethernet port as photo shows here.
- True-RMS measuring parameters
- ANSI and IEC 0.2 accuracy class
- Power quality analysis
- 4 quadrant energy
- 2MB onboard memory, can be extended to 16M
- Data logging
- High-speed RS485, Ethernet port (option)
- Measure individual harmonics from 2nd to 49th (option)
- TOU, 4 Tariffs, 6 Seasons, 6 Schedules
- Three years warranty
- With PC management software; web browse data
- Metering of distribution feeders, transformers, generators, capacitor banks and motors
- Medium and low voltage systems
- Commercial, industrial, utility
- Power quality analysis
- Data logging
- Monitoring system
PARAMETERS
Electrical parameters | |
---|---|
Power Supply (AC/DC) |
AC85-400V / DC85-330V Power consumption: <4VA |
Measurement Parameters |
Voltage (Ph-N); Voltage (Ph-Ph); Current; Frequency; PF; Active Power(W); Reactive Power(Q); Apparent Power(S), 2nd to 49th harmonics(option) |
Harmonics |
Total harmonics ratio of phase-voltage Total harmonics ratio of current 2nd to 49th harmonics ratio of phase-voltage 2nd to 49th harmonics ratio of current |
Maximum Value & Minimum Value | Voltage, current, frequency, active power, reactive power, apparent power,demandP,demandQ, demandS. |
Computation |
Forward active power energy Reverse active power energy Forward active power energy Reverse reactive power energy |
Measuring Range | 0-400V, 0-6A, 45-65Hz, -1 ~ 0 ~ 1 |
Measuring Accuracy |
Voltage: 0.5%RD±0.05%FS Current: 0.5%RD±0.05%FS Active Power: 0.5%RD±0.05%FS Reactive Power: 1.5%RD +0.05%FS Apparent power: 0.5%RD +0.1%FS Power Factor: 0.5%RD Frequency: 0.05%RD Active Energy: 0.5% |
Maximum Demand | Ia, Ib, Ic, ΣPtotal, ΣQtotal, ΣStotal, 15 minutes |
Display |
Blue back-lit LCD Display 5 display figures 4 operation keys |
Communication |
Support RS-485 interface port, 32 (128) Networking ModBus-TCP/IP SNMP communication protocol Ethernet 10/100M port (RJ45) |
Memory |
2M onboard memory,can be extended to 16M. Data looger interval can set by end users from 1min to 60min.The default is 15min. You can read the data through a PC, also you can select the data to diaplay and store from software. |
Programmable |
Measuring system: 3P4W/3P3W etc Transformation Ratio: PT 1-10000; CT 1-10000 |
Energy Pulse |
Provides active & reactive energy pulse output Pulse parameters can be choosed Range: 0.1-10000kWh/kvarh Dry contact output (1Ax100V) |
Connection Mode | 3P4W, 3P4W BAL, 3P3W, 3P3W BAL, 1P3W, 1P2W |
Baud | Baud: 1200-57600, Standard 38400 |
Mechanical parameters | |
Dimensions (L x W x H) (mm) | 96 x 96 x 12.8 |
Mounting |
Panel mounting Trepanning: 92x92mm The thickness of installation: 51mm |
Environmental conditions | |
Temperature | -5 to +50 °C |
Humidity | 20%-95%RH, without condensation |
Warranty | Three years warranty |
Parameters | Accuracy | Resolution | Measuring range | Show on the display |
---|---|---|---|---|
Voltage | 0.20% | 0.01V | 0-400V | 0.5-500kV |
Current | 0.20% | 0.01mA | 0-6.5A | 5mA-50000A |
Active power | 0.50% | 0.2W | 0-2400W/phase | -9999MW to +9999MW |
Reactive power | 2% | 0.2var | 0-2400var/phase | -9999Mvar to +9999Mvar |
Apparent power | 0.50% | 0.2VA | 0-2400VA/phase | 0-9999MVA |
Active demand | 0.50% | 0.2W | 0-2400W/phase | -9999MW to +9999MW |
Reactive demand | 2% | 0.2var | 0-2400var/phase | -9999Mvar to +9999Mvar |
Apparent demand | 0.50% | 0.2VA | 0-2400VA/phase | 0 to 9999MVA |
Power factor | 0.005 | 0.0001 | -2 | -2 |
Frequency | 0.01Hz | 0.01Hz | 45.000-65.000Hz | 45.000-65.000Hz |
Active energy | 0.5%,0.2% (Option) | 0.001kWh | 0-999999.999kWh | 0-99999999.9kWh |
Reactive energy | 2% | 0.001kvarh | 0-999999.999kvarh | 0-99999999.9kvarh |
Apparent energy | 0.50% | 0.001VAh | 0-999999.999kVAh | 0-99999999.9kVAh |
Phase angle | 0.1° | 0.01° | 0-359.99° | 0-359.99° |
Unbalance | 2% | 0.01% | 0-300.00% | 0-300.00% |
PT ratio | 1 | 1-10000 | ||
CT ratio | 1 | 1-10000 | ||
Address code | 1 | 1-253 |