INTRODUCTION:
TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity
of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value,
second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel.
TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need
large current.
PARAMETERS
TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity
of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value,
second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel.
TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need
large current.
PARAMETERS
Electrical parameters | |
---|---|
Accuracy | ±0.5% |
Power Supply(AC) |
220V±10%·25A, 50Hz/60Hz or 110V±10%·50A, 50Hz/60Hz |
Current Output (AC) | 1000A·5V or 500A·10V |
Capacity | 5KVA |
The current output waveform distortion | ≤5% |
Dual protection | overload electronic protection and software protection |
Primary current | |
Range | 0-1100A |
Resolution | 0.1A |
Accuracy | <0.5% |
Secondary measurement | |
Range | 0-6A |
Resolution | 0.001A |
Accuracy | <0.5% |
Current duration | |
1000A range |
1000A 2-3minutes 500A 3-6minutes |
500A range | 500A 2-3minutes |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 430×260×260 |
Weight(kg) | 28 |
Environmental conditions | |
Temperature | -10°C to 40°C |
Relative humidity | ≤80% |