Product Main

Quick Details

Application: Telecommunications
Type: On-line
Output Voltage: 110V-300V
Weight: different size with different weight
Protection: Unbalanced Loads
Phase: Single Phase
Brand Name: Ecsun
Place of Origin: China (Mainland)

Specifications

 

True double-conversion

Microprocessor control optimizes reliability

Input power factor correction

Output power factor 0.8

Wide input voltage (110 V – 300 V)

Converter mode available

ECO mode for energy saving

Generator compatible

Charger capacity expansion to 6A for long-run models
Smart SNMP works well with either USB or RS-232 together

Comprehensive display allows easy monitoring and access of UPS status

 

 


 

Model

 1K

 2K

 3K

1K (L)

2KL

3KL

PHASE

Single phase with ground

CAPACITY

1000 VA / 800 W

2000 VA / 1600 W

3000 VA / 2400 W

1000 VA / 800 W

2000 VA / 1600 W

3000 VA / 2400 W

INPUT

Nominal Voltage

200/208/220/230/240VAC

Voltage Range

110-300 VAC ± 5 %

Frequency Range

40Hz ~ 70 Hz

Power Factor

0.99 @ Nominal Voltage (100% Load)

OUTPUT

Output Voltage

200/208/220/230/240VAC

Voltage Requlation

± 1 %

± 3 %

Frequency Range 
(Synchronized Range)

47~ 53 Hz or 57 ~ 63 Hz

Frequency Range (Batt. Mode)

50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz

Overload

100%~110%:audible warning 110%~130%: UPS shut down in 30 seconds at battery mode or transfer to bypass when the utility is normal ;>130%:UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal

Current Crest Ratio

3:1

Harmonic Distortion

3 % THD (Linear Load) ;
6 % THD (Non-linear Load)

Transfer Time

AC to DC

Zero

Inverter to Bypass

4 ms (Typical)

Waveform (Batt. Mode)

Pure Sinewave

EFFICIENCY

To AC Mode

87%

90%

90%

85%

90%

To Battery Mode

83%

87%

89%

83%

87%

89%

BATTERY

Standard Model

Battery Type

12 V / 7 Ah

12 V / 7 Ah

12 V / 7 Ah

12 V / 7 Ah

-

-

Numbers

2

3

6

8

6

8

2

3

Typical Recharge Time

4 hours recover to 90% capacity

Charging Current (Max.)

1.0 A

Charging Voltage

27.3VDC ± 1%

41.0VDC ± 1%

82.1 VDC ±1%

109.4
VDC±
1%

82.1 VDC ±1%

109.4
VDC
±1%

27.3VDC
±1%

41.0 VDC
±1%

-

-

Long-run Model

Battery Type

Depending on the capacity of external batteries

Numbers

Charging Current (Max.)

1.0A/2.0A/4.0A/6.0 A ±10%

Charging Voltage

27.3 VDC ± 1%

41.0 VDC ± 1%

82.1 VDC ±1%

109.4
VDC
±1%

82.1 VDC ±1%

109.4
VDC
±1%

-

41.0 VDC ± 1%

82.1 VDC ±1%

109.4
VDC
±1%

82.1 VDC ±1%

109.4
VDC
±1%

INDICATORS

LCD or LED

Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators

ALARM

Battery Mode

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

Sounding twice every second

Fault

Continously sounding

PHYSICAL

Standard Model

Dimension, DxWxH (mm)

360x145x215

460x190x350

380 X 438 X 88

-

-

Net Weight (kgs)

10

13

33.5

 

33.5

 

10

13

Long-run Model

Dimension, DxWxH (mm)

360x145x215

460x190x350

N/A

380 X 438 X 88

480 X 438 X 88

Net Weight (kgs)

7.0

18.5

18.5

N/A

6.5

8.3

10

ENVIRONMENT

Humidity

20-90 % RH @ 0- 40°C (Non-condensing)

Noise Level

Less than 50dBA @ 1 Meter

MANAGEMENT

Smart RS-232/USB

Supports Windows? 2000/2003/XP/Vista/2008, Windows? 7/8, Linux, Unix, and MAC

Optional SNMP

Power management from SNMP manager and web browser