| Application: | Telecommunications |
|---|---|
| Type: | On-line |
| Output Voltage: | 110V-300V |
| Weight: | different size with different weight |
| Protection: | Unbalanced Loads |
| Phase: | Single Phase |
| Brand Name: | Ecsun |
| Place of Origin: | China (Mainland) |
Quick Details
Specifications
True double-conversion
Microprocessor control optimizes reliability
Input power factor correction
Output power factor 0.8
Wide input voltage (110 V – 300 V)
Converter mode available
ECO mode for energy saving
Generator compatible
Charger capacity expansion to 6A for long-run models
Smart SNMP works well with either USB or RS-232 together
Comprehensive display allows easy monitoring and access of UPS status
1K
2K
3K
1K (L)
2KL
3KL
PHASE
Single phase with ground
CAPACITY
1000 VA / 800 W
2000 VA / 1600 W
3000 VA / 2400 W
1000 VA / 800 W
2000 VA / 1600 W
3000 VA / 2400 W
INPUT
Nominal Voltage
200/208/220/230/240VAC
Voltage Range
110-300 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Power Factor
≧0.99 @ Nominal Voltage (100% Load)
OUTPUT
Output Voltage
200/208/220/230/240VAC
Voltage Requlation
± 1 %
± 3 %
Frequency Range
47~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Overload
100%~110%:audible warning 110%~130%: UPS shut down in 30 seconds at battery mode or transfer to bypass when the utility is normal ;>130%:UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal
Current Crest Ratio
3:1
Harmonic Distortion
≦ 3 % THD (Linear Load) ;
Transfer Time
AC to DC
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
To AC Mode
87%
90%
90%
85%
90%
To Battery Mode
83%
87%
89%
83%
87%
89%
BATTERY
Standard Model
Battery Type
12 V / 7 Ah
12 V / 7 Ah
12 V / 7 Ah
12 V / 7 Ah
-
-
Numbers
2
3
6
8
6
8
2
3
Typical Recharge Time
4 hours recover to 90% capacity
Charging Current (Max.)
1.0 A
Charging Voltage
27.3VDC ± 1%
41.0VDC ± 1%
82.1 VDC ±1%
109.4
82.1 VDC ±1%
109.4
27.3VDC
41.0 VDC
-
-
Long-run Model
Battery Type
Depending on the capacity of external batteries
Numbers
Charging Current (Max.)
1.0A/2.0A/4.0A/6.0 A ±10%
Charging Voltage
27.3 VDC ± 1%
41.0 VDC ± 1%
82.1 VDC ±1%
109.4
82.1 VDC ±1%
109.4
-
41.0 VDC ± 1%
82.1 VDC ±1%
109.4
82.1 VDC ±1%
109.4
INDICATORS
LCD or LED
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continously sounding
PHYSICAL
Standard Model
Dimension, DxWxH (mm)
360x145x215
460x190x350
380 X 438 X 88
-
-
Net Weight (kgs)
10
13
33.5
33.5
10
13
Long-run Model
Dimension, DxWxH (mm)
360x145x215
460x190x350
N/A
380 X 438 X 88
480 X 438 X 88
Net Weight (kgs)
7.0
18.5
18.5
N/A
6.5
8.3
10
ENVIRONMENT
Humidity
20-90 % RH @ 0- 40°C (Non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB
Supports Windows? 2000/2003/XP/Vista/2008, Windows? 7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
(Synchronized Range)
≦ 6 % THD (Non-linear Load)
VDC±
1%
VDC
±1%
±1%
±1%
VDC
±1%
VDC
±1%
VDC
±1%
VDC
±1%