Operating Temperature: | -30--60 |
---|---|
Temperature Coefficient: | 40 |
Rated Power: | 6.6-66 |
Resistance Tolerance: | 1% |
Resistance: | as volatge |
Package Type: | Surface Mount |
Technology: | Cermet |
Type: | Humidity Sensitive Resistor |
Model Number: | THT-ZT |
Brand Name: | TWHT |
Place of Origin: | China (Mainland) |
Quick Details
Specifications
General Description
Neutral grounding resistors Our company manufactures can be used for indoor and outdoor and the neutral point is connected with a porcelain bushing or with a high voltage cable from the bottom, top or side. The most common protection degree preferred for Neutral Grounding Resistors is IP23 as it allows the resistor elements to cool easier and they can be used both at sea shores and deserts because the resistor elements are completely stainless steel and does not affected by extreme conditions. MINGRUI provides complete technical assistance in order to meet your specifications or site conditions.
Technical Specifications
Operation voltage: up to 110kV line to line system
Rated current(A): up to 2000
Ambient temperature: less than 55 centigrade
Resistance alloy: Stainless steel
Protection degree: IP23(Outdoor) and others
Features
2mm hot dip galvanized steel enclosure
Stainless steel or aluminum enclosure are available on demand
Typically, RAL7032 paint for enclosure (other colors are available on demand)
Solid top cover sloped to prevent water accumulation
Custom made lifting eye bolts for securing lifting
Front cover for easy access to connection and inspection doors available on demand
Corrosion resistant stainless steel nameplate
Options
Elevated support standard are provided for ground clearance and safety
Specially designed units for hazardous and extreme locations
Stainless steel or aluminum enclosure on demand
Installation of voltage transformer
Installation of protection relays
Porcelain entrance bushing can be mounted on top or on the side of Neutral Grounding Resistor
Grounding transformer installation
Motorized or manual single pole disconnector switches, load banks switches, surge arresters and heaters in the neutral grounding resistors.
Selection Details
System voltage
Line to neutral voltage
Desired current rating
Desired resistance level
Maximum time ON(seconds)
Bushing entry or cable entry
Current transformer ratio (if applicable)
Disconnector switch (if applicable)