Specifications

HACT series provide precision measurement for energy monitoring applications to sensing power loading equipment without interrupting the lines. It has been specifically designed to be easy to open and yet maintain the accuracy required for intelligent meters, quick to fit around cables.


Features:
1:
Reliable locking mechanism                           

2:Ergonomic design
3:Precision measurement and low phase shift
4:Quick connec terminals(if required)

Applications:

1: Energy and sub-metering products
2: Electrical load monitoring
3: Network equipment
4: Measurement instruments

Specifications :

MODEL

HACT

Current Ratio

300A/100mA

400A/40mA

500A/50mA

600A/60mA

300~600/0.333V

Primary Current(A)

300A

400A

400A

600A

300A~600a

Max. Current(A)

360

480

600

720

720

Secondary Current(mA)

100mA

40mA

50mA

60mA

0.333V

Load Resistance(Ω)

50Ω

50Ω

50Ω

50Ω

/

Class

0.5/1.0

0.5/1.0

0.5/1.0

0.5/1.0

0.5/1.0

Turns Ratio

3000:1

10000:1

10000:1

10000:1

/

Protection Level

7.5V0-P

7.5V0-P

7.5V0-P

7.5V0-P

 

Insullation Category

CAT

Operating Condition

-20+50,≤85%RH,No condensation,IN-house&Any direction installable

Storage Condition

-30+50,≤85%RH,No condensation


Material List:

NO

ITEM

DESCRIPTION

UL Card

MATERIAL

NOTE

1

CORE

UU20.6

/

N07

2

CASE

PP6331

E85783

PP

3

BOBBIN

D202G15

E107536

PBT

4

WIRE

2UEW

E164502

UEW/U

5

LEAD WIRE

UL1015 22AWG

E189674

PVC

105 600V

6

SOLDER

99.30%

/

Sn