Coil Number: | Autotransformer |
---|---|
Coil Structure: | Toroidal |
Phase: | Single |
Usage: | Current |
Model Number: | HACT |
Brand Name: | HEYI |
Place of Origin: | China (Mainland) |
Shell Color: | Black |
Frequency: | 50/60Hz |
Accuracy Class: | 0.5/1.0 |
Approval: | CE, Rohs |
Quick Details
Specifications
HACT series provide precision measurement for energy monitoring applications to sensing power loading equipment without interrupting the lines. It has been specifically designed to be easy to open and yet maintain the accuracy required for intelligent meters, quick to fit around cables.
Features:
1:Reliable locking mechanism
2:Ergonomic design
3:Precision measurement and low phase shift
4:Quick connec terminals(if required)
Applications:
1: Energy and sub-metering products
2: Electrical load monitoring
3: Network equipment
4: Measurement instruments
Specifications :
MODEL |
HACT |
||||
Current Ratio |
300A/100mA |
400A/40mA |
500A/50mA |
600A/60mA |
300~600/0.333V |
Primary Current(A) |
300A |
400A |
400A |
600A |
300A~600a |
Max. Current(A) |
360 |
480 |
600 |
720 |
720 |
Secondary Current(mA) |
100mA |
40mA |
50mA |
60mA |
0.333V |
Load Resistance(Ω) |
50Ω |
50Ω |
50Ω |
50Ω |
/ |
Class |
0.5/1.0 |
0.5/1.0 |
0.5/1.0 |
0.5/1.0 |
0.5/1.0 |
Turns Ratio |
3000:1 |
10000:1 |
10000:1 |
10000:1 |
/ |
Protection Level |
7.5V0-P |
7.5V0-P |
7.5V0-P |
7.5V0-P |
|
Insullation Category |
CATⅢ |
||||
Operating Condition |
-20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable |
||||
Storage Condition |
-30℃~+50℃,≤85%RH,No condensation |
Material List:
NO |
ITEM |
DESCRIPTION |
UL Card |
MATERIAL |
NOTE |
1 |
CORE |
UU20.6 |
/ |
N07 |
|
2 |
CASE |
PP6331 |
E85783 |
PP |
|
3 |
BOBBIN |
D202G15 |
E107536 |
PBT |
|
4 |
WIRE |
2UEW |
E164502 |
UEW/U |
|
5 |
LEAD WIRE |
UL1015 22AWG |
E189674 |
PVC |
105℃ 600V |
6 |
SOLDER |
99.30% |
/ |
Sn |