Product Main

Quick Details

Application: Computer
Type: On-line
Output Voltage: 220V
Protection: Short Circuit
Phase: Single Phase
Model Number: Green Star Series
Brand Name: UPSEN
Place of Origin: China (Mainland)

Specifications

Key Features         
 1:True double-conversion on line UPS            
 2:System efficiency high up to 90%        
 3:Advanced Current Control     
 4:Active input power factor correction 0.99            
 5:With external battery,it is convenient for user to expand use time and backup power time     
 6:50Hz/60Hz frequency converter mode      
 7:Adjustable battery number from 16 pcs to 20 pcs            
 8:Large blue ground LCD digital display shows Detailed Real-Time UPS Status and parameters     
 9:Excellent Protection against over voltage, over load, over current, over charge and so on.           
10:Emergency power off function (EPO)             
11:3-stage extendable charging design for optimized battery performance            
12:Maintenance bypass available            
13:Adjustable charging current via LCD or software (0.5A~6A)    

Applications
Home, Office, Computer, PC, Data Room, Communication, Server,ATM, Bank System, School, CCTV, Security System, Alarm System etc.

Technical Specification
    
GREEN STAR 6K/10K ONLINE UPS SPECIFICATION
MODEL G6K (L) G10K (L)
PHASE 1 phase in / 1 phase out
CAPACITY 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Nominal Voltage  208/220/230/240VAC
Voltage Range Low Line Loss  110 VAC ± 3% at 50% Load
176 VAC ± 3% at 100% Load 
Low Line Comeback  120 VAC ± 3% at 50% Load
186 VAC ± 3% at 100% Load 
High Line Loss  300 VAC ± 3% 
High Line Comeback  290 VAC ± 3% 
Frequency Range
46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Power Factor >= 0.99  @ 100% load
OUTPUT
Nominal Voltage  208/220/230/240VAC
AC Voltage Regulation  ± 1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion <= 3 % THD (Linear Load)  
<= 6 % THD (Non-linear Load)
Transfer Time
Bypass to Inverter 
(Line mode)

Zero

Inverter to Bypass 
(Line mode)

Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
Line Mode 89% 90%
Battery Mode 88% 89%
BATTERY
Standard Model Battery Type 12 V / 7 AH 12 V / 9 AH
Numbers 16 16
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current 
Default:1.0 A ±  10%,           
Max.:2.0A ±  10%

Default:1.0 A ±  10%,          
Max.:2.0A ±  10%

Float Charging Voltage 
218.4 VDC ±  1%
Long-run Model Battery Type Depending on applications
Numbers 16-20** (adjustable)
Charging Current  Default:4.0 A ±  10%,  Max.:6.0A ±  10%
Default:4.0 A ±  10%,           
Max.:6.0A ±  10%

Float Charging Voltage 
273 VDC ±  1% (based on 20 pcs batteries)
INDICATORS
LCD Panel
UPS status, Load level, Battery level, Input/Output voltage, 
Discharge timer, and Fault conditions

ALARM
Battery Mode Sounding every 4 seconds
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model
Dimension, 
D X W X H (mm)

369 x 190 x 688
442 x 190 x 688
Net Weight (kgs) 60 75
Long-run Model
Dimension, 
D X W X H (mm)

369 x 190 x 318
442 x 190 x 318
Net Weight (kgs) 21 23
ENVIRONMENT
Operation Humidity 0-95 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 55dBA @ 1 Meter
Less than 58dBA 
@ 1 Meter

MANAGEMENT
Smart RS-232/USB
Supports Windows? 2000/2003/XP/Vista/2008, 
Windows? 7/8, Linux, Unix, and MAC

Optional SNMP
Power management from SNMP manager and web browser