Product Main

Quick Details

Application: Security / Monitoring / Alarm
Type: On-line
Output Voltage: 400v
Protection: Overvoltage
Phase: Three Phase
Model Number: High Efficiency Strar Series
Brand Name: upsen

Specifications

Industrial Environments Online 10K-200K Low Frequency UPS with High-efficient DSP chip
Model: Low Frequency Online UPS High Efficiency Strar Series HE33 10K-200K(3Ph in/3Ph out)


Application
Computer room,Data center,Precision instrument, Hospital ICU, CT ,Dsa, Nmr, Color Doppler Imagining,Commercial facility,Intelligent equipment ect
 
Key Features
1:DSP control
2:Easy to maintain (front access)
3:Flexible battery arrangement 
4:Compatible with generator
5:Manual maintenance bypass
6:Up to 8 units in parallel
7:Manual maintenance bypass
8:Battery can be sharing
9:Intelligent management of battery charging and discharging
10:Back feed protection: to avoid energy feeding back into the mains supply
11:Full protection against over-discharge, overcharge, over load

Technical   Specification


High Efficiency Strar Series HE33 10K-200K

Model

HE33 Series UPS

Capacity (VA)

10K

15K

20K

30K

40K

60K

80K

100K

120K

160K

200K

Noninal output capacity

8KW

12KW

16KW

24KW

32KW

48KW

64KW

80KW

96KW

128KW

160KW

Operate type

Double conversion online type

Input

Nominal voltage

220V/380, 230/400, 240/415V 

Voltage Tolerance

380/400/415V±25%

Frequency

50Hz/60Hz±5%

Permitted Frequency Tolerance

±2% (selectable from ±1% to 5% from the front panel)

Soft start

0-100% in 30" (selectable)

Input power factor

0.95(with input filter)

Standard features

Back Feed protection separable bypass line

 

Phase

Three phase +N+G

Output

Voltage

220V/380, 230/400, 240/415V, ±1% (stable load), ±5%(active load)

Frequency

50/60Hz (±5%, AC mode), 50/60Hz (±1%, Battery mode)

Static stability

±5% in 19ms

Distortion

Linear load <3%, non linear load<5%

Power factor

0.8

Output wave

Pure sine wave

Crest factor

3:01

Battery voltage

Standard battery voltage

384V

432V

480V

Floating charge

432V

486V

540

Terminal voltage

336V

378V

420V

Charge current

1A-50A (Can calculate and set according to battery configuration software)

Maximum Discharge Current

28

42

56

85

113

169

225

282

338

381

507

Main Function

Active voltage change

0-100%±5%

Instant recover time

<10ms

Imbalance voltage

<±5%,<±1%( Balance load voltage)

Overload capacity

125%→10min,150%→1min

Static switch

Automatic

Protection

UPS over current, short circuit, battery low voltage, over heat

Cold method

Compel aeration ( temperature control mode)

Noise

60-65dB

Display

LED,LCD display

Remote signalling

Voltage-free contacts

Remote commands

EPO and bypass

Communication Port (Optional)

double RS232 + remote contacts + 2 communication interface slots

Alarm

Alarm with buzzer and indicators

Environment

Temperature: 0-40C  Humidity: 0-90%

*Specification are subject to change without prior notice