| Brand Name: | konan |
|---|---|
| Temperature of Media: | High Temperature |
| Material: | Stainless Steel |
| Pressure: | Medium Pressure |
| Standard or Nonstandard: | Standard |
| Model Number: | SAF100-5 |
| Place of Origin: | Japan |
Quick Details
Specifications
Intrinsic safety explosion barrier is an explosion-proof device with single channel, Zener-diode DC circuit that enables interactive electric signaling without short circuit while controlling energy transmission in order to prevent ignition in explosive atmosphere.
1.Applicable to Zone 0.
2.A-class ground is not necessary since the input and output are insulated
each other.
3.When serially connected to a transmission circuit, the barrier protects
the circuit and components in hazardous area from being affected by
a serious accident in the non-hazardous area.
4.Despite in the hazardous location, conventional wiring is available.
5.Intrinsical proof of operational signal is figured out easily and at lower
cost.
6.SAF100-5 safety barrier employ crimping terminal wiring method.
7.as SAF100-5 safety barrier has protection circuit, it will be not broken
if you wired in the wrong polarity.
8.LED indicates the condition of the input and output
Model code 100-5
Explosion-proof construction Intrinsic safety construction(EⅡC)
Rated voltage 24±10%
Maximum voltage of a intrinsic safety circuit 29.4
Max. Allowable voltage 25.95
Maximum current of a intrinsic safety circuit 93.8
Electric power of a intrinsic safety circuit 0.689W
Ambient temp. -2050℃
Basic circuit figure
Does not need A-class ground.
Operating condition
1.Place the valve in non-hazardous area.
2.Perform single grounding using type A ground.
3. Parts and connections cannot be changed.
4. Use with specified solenoid valves.
5. Allowable inductance for external
connection: 2mH / Capacitance: 0.05 μF
14. Konan Intrinsic Safety Solenoid Valves Explosion barrier SAF3-5, MTL728+
Intrinsic safety explosion barrier is an explosion-proof device with single channel, shunt-diode DC circuit that enables interactive electric signaling without short circuit while controlling energy transmission in order to prevent ignition in explosive atmosphere.
1.Applicable to Zone 0.
2.When serially connected to a transmission circuit, the barrier protects
the circuit and components in hazardous area from being affected by
a serious accident in the non-hazardous area.
3.Despite in the hazardous location, conventional wiring is available.
4.Intrinsical proof of operational signal is figured out easily and at lower
cost.
5.as SAF3-5 safety barrier has protection circuit, it will be not broken
if you wired in the wrong polarity.
6.SAF3-5 safety barrier employ crimping terminal wiring method.
Model code 3-5 728+
Explosion-proof construction
Intrinsic safety construction(ExiaⅡB) Intrinsic safety construction(i2G4)
Rated voltage 24±5%-
Max. Working voltage - 25.5
Max. Allowable voltage - 26.6
Safety retention voltage /250
Rating of a fuse 50
Ambient temp. -2060℃ -1060℃
Basic circuit figure
Operating condition
1.Place the valve in non-hazardous area.
2. Parts and connections cannot be changed.
3. Use with specified solenoid valves.
4. Allowable inductance for external connection: 10mH / Capacitance: 0.5 μF
4. Allowable inductance for external connection: 1mH / Capacitance: 0.05 μF