| Jacket: | PVC |
|---|---|
| Conductor Material: | Aluminum |
| Application: | Power Station |
| Type: | Medium Voltage |
| Insulation Material: | XLPE |
| Model Number: | 50 sq mm XLPE insulated armored cable |
| Brand Name: | 50 sq mm XLPE insulated armored cable |
| Place of Origin: | China (Mainland) |
Quick Details
Specifications
Standard:National Standard GB/T12706-2008,IEC60502
Rated Voltage: U0/U: 3.6/6kV~26/35kV
Construction :
|
Conductor |
Compact Stranded Copper Conductor, Class 2 as per IEC 60228 |
|
Circular solid Copper Conductor, Class 1 as per IEC 60228 |
|
|
Flexible Stranded Copper Conductor, Class 5 as per IEC 60228 |
|
|
Conductor Screen |
Semi-conductor (MV only) |
|
Insulation |
XLPE(Cross-linked polyethylene) |
|
Insulation Screen |
Semi-conductor (MV only) |
|
Separate Screen |
Copper Tape (MV must, LV optional) |
|
Filler |
PP Yarn, or Paper |
|
Wrapping Tape |
PP |
|
Inner Covering |
Extruded PVC (MV only) |
|
Armour |
Steel Wire, or Steel Tape, or Aluminium Tape optional |
|
Overall Sheath |
PVC or PE |
Application:
Suitable for use in power distribution lines or fixed installation with rated voltage between 3.6/6kV~26/35kV
Operating Characteristics:
Max.permission conductor continous operating temperature of conductor;90 °C
Max.short-circuit temperature of conductor shall not exceed 250 °C (5s maximum duration)
The ambient temperature under installation of cable should not below 0 °C
The bending radius of a single-core cable should not less than 20 times of outer diameter of the cable
The bending radius of a three-core cable should not less than 15 times of outer diameter of the cable
Operating condition when cable laying
Max.permission continous operating temperature of conductor:90 °C
Ambient air temperature:40 °C
Soil temperature:20 °C
Thermal resistivity of soil:1.0V.m/w
Depth of laying :0.8m
Only consider a loop
Single-core cable is horizontal laid, adjacent space is equivalent to the diameter of the cable