Product Main

Quick Details

Application: Security / Monitoring / Alarm
Type: On-line
Output Voltage: 100/110/115/120/127VAC or 200/208/220/230/240VAC
Protection: Overcurrent
Phase: Single Phase
Model Number: Green Star Series
Brand Name: UPSEN
Place of Origin: China (Mainland)
Transfer Time: Zero
Voltage Regulation: 1%
Noise Level: Less Than 50dba
Frequency Range: 40Hz ~ 70 Hz

Specifications

3000VA/2400W Pure Sine Wave Online UPS for Printing machines 
Model:High Frequency Online UPS Green Star Series 1K-3Kva (1ph in/1ph out)
 
Key Features    
1:True online double conversion technology     
2:Supports motor load and generator.
3:Input power factor correction     
4:Output power factor 0.8    
5:Wide input voltage (110 V - 300 V)     
6:Converter mode available    
7:Pure sine wave output
8:Generator compatible     
9:Charger capacity expansion to 6A for long-run models     
10:Smart SNMP works well with either USB or RS-232 together    
11:Highest reliability and maximum performance for power sharing and redundancy
 
UPS Application areas:
1).CNC machines
2).Textile machinery
3).Lifts & elevators
4).Air conditioning package units and plants
5).Large deep freezers
6).Medical equipments
7).Communication equipments
8).Entire LT line stabilisation for factories / buildings / housing societies
9).Printing machines
10).Packaging machines
11).Any other microprocessor based machines
 
Technical Specification

GREEN STAR ONLINE UPS SELECTION GUIDE
MODEL G1K (L) G2K (L) G3K (L)
PHASE Single phase with ground
CAPACITY 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W
INPUT
Nominal Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
Input Voltage Range  55-145 VAC or 110-300 VAC 
Frequency Range
40Hz  ~ 70 Hz
Power Factor >= 0.99 @ Nominal Voltage (100% load)
OUTPUT
Output Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
Voltage Regulation  ± 1%
Frequency Range (Synchronized Range) 47~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion <= 3 % THD (Linear Load); <= 6 % THD (Non-linear Load)
Transfer Time AC to DC Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
To AC Mode 88% 89% 90%
To Battery Mode 83% 87% 88%
BATTERY
Standard Model Battery Type 12 V / 9 AH 12 V / 7AH 12 V / 7 AH
Numbers 2 6 6
Typical Recharge Time 4 hours recover to 90% capacity
Charging Current (max.) 1.0 A
Charging Voltage 27.4VDC ± 1% 82.1 VDC ±1% 82.1 VDC ±1%
Long-run Model* Battery Type Depending on the capacity of external batteries
Numbers 3 6 8
Charging Current (max.) 1.0A/2.0A/4.0A/6.0 A
Charging Voltage 41.0VDC ± 1% 82.1 VDC ±1% 109.4VDC ±1%
INDICATORS
LCD
Load level, Battery level, AC mode, 
Battery mode, Bypass mode, and Fault indicators

ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding
PHYSICAL
Standard Model Dimension, D x W x H (mm) 397 X 145 X 220 419X190X318
Net Weight (kgs) 13 26 28
Long-run Model* Dimension, D x W x H (mm) 282 x 145 x 220 397 X 145 X 220
Net Weight (kgs) 4.6 6.8 7.4
ENVIRONMENT
Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser

 
* Long-run model is only available in 200/208/220/230/240VAC systems.