| Application: | Networking |
|---|---|
| Type: | On-line |
| Protection: | Overvoltage |
| Phase: | Three Phase |
| Model Number: | Legend Strar Series |
| Brand Name: | UPSEN |
| Place of Origin: | China (Mainland) |
| Wide Input Range: | Have |
| Optional: | Snmp Card |
| Waveform: | Pure Sine Wave |
| Input Power Factor: | Input Power Factor |
Quick Details
Specifications
380V LCD Online Low Frequency UPS 30kVA 24kw for Financial
Model:Low Frequency Online UPS Legend Strar Series LS33 10K-80K(3Ph in/3Ph out)
Key Features
1:True onlin double conversion completely isolates the load from various grid faults and pollution
2:Sufficient Expansion Slots
3:True galvanic isolation transformer design
4:Control designed to withstand all kinds of loads
5: SNMP card(optional) for web-based monitoring
6:perfect for the most demanding and delicate of applications
7:Isolation transformer is included for all models
8:Accept dual-mains input
9: Intelligent battery management to prolong battery lifecycle
10:The low frequency UPS is mature electric equipment and the reliability is very high and well known
Applications:
Data center, Industrial equipment, Financial , Large Data rooms,electric equipments, medical equipments, instruments,Commercial tax affair,etc.
Technical Specification
Model:Low Frequency Online UPS Legend Strar Series LS33 10K-80K(3Ph in/3Ph out)
Key Features
1:True onlin double conversion completely isolates the load from various grid faults and pollution
2:Sufficient Expansion Slots
3:True galvanic isolation transformer design
4:Control designed to withstand all kinds of loads
5: SNMP card(optional) for web-based monitoring
6:perfect for the most demanding and delicate of applications
7:Isolation transformer is included for all models
8:Accept dual-mains input
9: Intelligent battery management to prolong battery lifecycle
10:The low frequency UPS is mature electric equipment and the reliability is very high and well known
Applications:
Data center, Industrial equipment, Financial , Large Data rooms,electric equipments, medical equipments, instruments,Commercial tax affair,etc.
Technical Specification
|
3P/3P ONLINE UPS SELECTION GUIDE |
||||||||
| LS33 Series 10K - 80Kva | ||||||||
| MODEL | 10K | 20K | 30K | 40K | 60K | 80K | ||
| CAPACITY | 10KVA/ 8KW | 20KVA/ 16KW |
30KVA/ 24KW |
40KVA/ 32KW |
60KVA/ 48KW | 80KVA/ 64KW | ||
| INPUT | ||||||||
| Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||
| Acceptable Voltage Range | 305VAC ~ 460VAC | |||||||
| Frequency | 46-54Hz or 56-64Hz | |||||||
| INVERTER | ||||||||
| Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||
| Precision |
Stationary: ±1% Transitory: ±5% (load variations 100-0-100%) |
|||||||
| Frequency |
50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz |
|||||||
| Max. Synchronisation Speed | ±1 Hz/s | |||||||
| Waveform | Pure Sinewave | |||||||
| Total Harmonic Distortion (THDv) |
<2% (Linear Load) <5% (Non-linear Load) |
|||||||
| Phase Displacement |
120o ±1% (balanced load) 120o ±2% (imbalances 50% of the load) |
|||||||
| Dynamic Recovery Time | 1 cycle at 98 % of the static value | |||||||
| Admissible Overload | 110% for 10min; 150% for 60sec ; >160% for 200ms | |||||||
| Admissible Crest Factor | 3:1 | |||||||
| Admissible Power Factor | 0.6~1 (inductive or capacitive) | |||||||
| Imbalance Output Voltage @ 100% Unbalanced Load | <1% | |||||||
| Current Limit |
High overload, short-circuit: RMS Voltage Limit High Crest-Factor current: Peak Voltage Limit |
|||||||
| STATIC BYPASS | ||||||||
| Type | Solid state | |||||||
| Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||
| Frequency | 50/60 Hz | |||||||
| Activation Criterion | Microprocessor control | |||||||
| Transfer Time | Zero | |||||||
| Admissible Overload | 150% for 1 hour; 180% for 30sec; >200% for 200ms | |||||||
| Transfer to Bypass | Immediate, for overloads above 160% | |||||||
| Retransfer | Automatic after alarm clear | |||||||
| MAINTENANCE BYPASS | ||||||||
| Type | Without interruption | |||||||
| Voltage | 3 x 400V (3Ph + N) | |||||||
| Frequency | 50/60 Hz | |||||||
| Overall Efficiency | Line Mode | 90% | 91% | 92% | 93% | |||
| Battery Mode | 90% | 91% | 93% | 93% | ||||
| BATTERY & CHARGER | ||||||||
| Battery Type and Numbers | 12VDC x 16 pcs | 12VDC x 32 pcs (29~32 pcs adjustable) | ||||||
| Nominal Battery Voltage | 192 VDC | 384 VDC (Based on 32pcs batteries) | ||||||
| Charging Method | CC/CV | |||||||
| Precision | ±1% | |||||||
| Charging Current | Max.: 40 A | |||||||
| Charging Voltage | 216 VDC | 432 VDC (Based on 32pcs batteries) | ||||||
| PHYSICAL | ||||||||
| Dimensions, D x W x H(mm) | 656 x 405 x 817 | 656 x 405 x 941 | 840 x 432 x 1140 | 975 x 554 x 1286 | ||||
| Net Weight (Kgs) | 180 | 205 | 295 | 330 | 451 | 519 | ||
|
* Product specifications are subject to change without further notice |
||||||||