Main Features
- True double-conversion
- DSP technology guarantees high performance
- Output power factor 0.8
- Wide input voltage range (110-300 VAC)
- Active power factor correction in all phases
- Built-in phase auto adapt function simplifies wire installation
- 50Hz/60Hz frequency converter mode
- Eco mode operation for energy saving (ECO)
- Emergency power off function (EPO)
- Generator compatible
- SNMP+USB+RS-232 multiple communications
- 3-stage extendable charging design for optimized battery performance
- Adjustable battery numbers
- Optional N+X parallel redundancy
| Model | Galleon 3/1-10KR (L) | Galleon 3/1-15KR (L) | Galleon 3/1-20KR (L) | |
| PHASE | 3-phase in / 1-phase out | |||
| CAPACITY | 10000 VA/8000 W | 15000 VA/12000 W | 20000 VA / 16000 W | |
| INPUT | ||||
| Nominal Voltage | 3 x 400 VAC (3Ph+N) | |||
| Voltage Range | 305-478 VAC (3-phase) at 100% load ; 190-520 VAC (3-phase) at 50% load | |||
| Frequency Range | 46~54 Hz or 56~64Hz | |||
| Power Factor | > 0.99 @ 100% Load | |||
| THDi | < 6% @ 100% Load | |||
| OUTPUT | ||||
| Output Voltage | 208/220/230/240VAC | |||
| AC Voltage Regulation (Batt. Mode) | ± 1% | |||
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||
| Current Crest Ratio | 3:1 | |||
| Harmonic Distortion | < 2 % THD (Linear Load) ; <5 % THD (Non-linear Load) | |||
| Transfer Time | AC Mode to Batt. Mode | Zero | ||
| Inverter to Bypass | Zero | |||
| Waveform (Batt. Mode) | Pure Sinewave | |||
| EFFICIENCY | ||||
| AC Mode | 89% | |||
| Battery Mode | 86% | 88% | 87% | |
| BATTERY | ||||
| Standard Model | Battery Type | 12 V / 7Ah | ||
| Numbers | 20 (18 - 20 adjustable) | 20 pcs x 2 strings (18 - 20 adjustable) | ||
| Typical Recharge Time | 9 hours recover to 90% capacity | |||
| Charging Current (Max.) | 1A | 2A | ||
| Charging Voltage | 273 VDC ± 1% (based on battery numbers at 20 pcs) | |||
| Long-run Model | Battery Type | Depending on the capacity of external batteries | ||
| Numbers | ||||
| Charging Current (Max.) | 4A | |||
| Charging Voltage | 273 VDC ± 1% (based on battery numbers at 20 pcs) | |||
| INDICATORS | ||||
| LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||
| ALARM | ||||
| Battery Mode | Sounding every 4 seconds | |||
| Low Battery | Sounding every second | |||
| Overload | Sounding twice every second | |||
| Fault | Continously sounding | |||
| PHYSICAL | ||||
| Standard Model | Dimension, DxWxH (mm) |
UPS unit:500x248x563(3U) Battery pack: 580 x 438 x 133(3U) |
UPS unit:500x248x563(6U) Battery pack: 580 x 438 x 133(3U) x 2PCS |
|
| Net Weight (kgs) |
UPS unit: 27 Battery pack: 63 |
UPS unit: 45 Battery pack: 63 x 2PCS |
||
| Long-run Model | Dimension, DxWxH (mm) | 500x248x563(3U) | 500x248x563(6U) | |
| Net Weight (kgs) | 27 | 35 | ||
| ENVIRONMENT | ||||
| Operation Humidity | 0-95 % RH @ 0- 40°C (Non-condensing) | |||
| Noise Level | Less than 60dB @ 1 Meter | Less than 65dB @ 1 Meter | ||
| MANAGEMENT | ||||
| Smart RS-232/USB | Supports Windows? 2000/2003/XP/Vista/2008, Windows? 7/8, Linux, Unix, and MAC | |||
| Optional SNMP | Power management from SNMP manager and web browser | |||
| * L means long-run model |
| * Product specifications are subject to change without further notice |