Product Main

Quick Details

Dimensions: D=1.5~8.93m
Application: Air conditioning cooling system, refrigeration series,foaming
Model Number: C7010
Brand Name: WJ
Place of Origin: China (Mainland)

Specifications

(1)  Industrial Tower:

Air wet bulb temperature T=28℃;

Into the tower water temperature T=42℃;

Out of the tower water temperature T=32℃;

(2)  Civil Tower:

Air wet bulb temperature T=28℃;

Into the tower water temperature T=37℃;

Out of the tower water temperature T=32℃;

Code is as follows:

( 1 )  The water temperature drop:

   Medium High energy-saving cooling(Design temperature drop of 10 to 25 degrees) J -Energy Saving

    Medium and high cooling(Temperature drop of 10 to 25 degrees) Code-G represents

( 2 )  Tower components:

   L-Anhydrous plate

   DP-shallow water plate

   GP-Deep water plate(Effective water in the depth of 400 mm, If required to increase the depth of the water, the order should be put forward)

   FN-Square counter current type of steel structure

Selection and Use:

Know the amount of cooling water-Q, into  the tower water temperature-t1, Out of the tower water temperature-t2,  and the air wet bulb temperature-T. according to this description of the thermal performance curve to determine the specifications of the tower. The cooling tower materials can be negative 50 degrees, but for average temperature below minus 10 degrees region ordering, it is better for explanation advance. And it can be convenient to take anti-icing measures.So the cooling tower cost need to increase.

The turbidity of circulating water is no more than 50mg/1 short-term is no more than 100mg/1. It should not contain oil and mechanical impurities.Need to take out the algae and water quality stability measures if necessary.

Cooling tower inlet and outlet direction can be 90 °, 180 °, 270° rotation, The cloth water system is designed according to the nominal amount of water,such as the name of the actual amount of water and water for more than a difference of±15%,in order to modify the design when ordering.Cooling tower inlet water temperature is not more than 60 degrees, if it is more than 60 degrees when the order should be explained.

Fan blade installation angle can be adjusted, but to ensure that the angle of the same, and the motor current is not exceed the motor rated current.

The wind turbine can be used for a short time to reverse the ice.

When using the cooling tower's water dish to make the pool, the " self-water" , " rapid water supply" , " outfall" and the " overflow pipe" should be installed.When ordering must be specifically asked because cooling towers offer does not include this part of the price.

The cooling tower components in the storage and transportation process, it may not be heavy pressure, not exposure, and pay attention to the fire. Cooling tower installation, transportation, maintenance process may not use electricity, gas welding and other open flames shall not be set off firecrackers fireworks nearby. If there is fire retardant requirement, it should be put forward when ordering.

This kind of tower's transport weight is calculated according to the packing water film thickness 0.5mm, and no weight is considered for the weight of the other impurities. If the water quality is poor, we recommend an appropriate increase in wet weight. The basis weight of the load has been calculated by scaling.