Dimensions: | 32cm*24cm*13cm |
---|---|
Operating Temperature: | -10 grade to +40 grade |
Output Voltage: | 0 to 400V |
Accuracy Class: | 0.05% |
Measuring Energy Range: | 10000KW |
Phase: | Three Phase |
Display Type: | Analog and Digital |
Model Number: | NADS |
Brand Name: | NAELECTRIC |
Place of Origin: | China (Mainland) |
Three-phase Watt-hour Meter Calibrator: | Three-phase Power Meter Calibrator |
3-phase Energy Meter On-site Calibrator: | Meter On-site Calibrator |
3-phase Energy Meter: | On-site Calibrator |
Quick Details
Specifications
Characteristics of the products
(1) The instrument is a high precision measuring instrument, which can be used in the calibration of electric energy meter, testing of electrical parameters, detection of waveform distortion, voltage fluctuation, unbalanced three-phase and other power quality problems occurred in the power grid.
(2) The instrument can detect the integrated error of measuring equipment on line on the case of no power failure, without changing the measuring circuit and do not open the metering equipment.
(3) The precise measurement of voltage, current, active power, reactive power, phase angle, power factor, frequency and other electrical parameters to calculate the measurement error of the test equipment circuit.
(4) With optional virtual load box, when the user without load or with ultra-low load, the instrument also can accurately measure the energy meter.
(5) It can display the measured voltage and current vector diagram, the user can analyze the wiring of the measuring equipment is correct or not through the analysis of vector diagram. Meanwhile, when in the three-phase three-wire connection mode, it can automatically determine 48 kinds of wiring; Automatic calculation function of electricity compensation facilitates the operator to calculate the electricity compensation for the user whose wiring has problem.
(6) Clip-on transformer is used to measure the current circuit, the operator does not need to disconnect the current circuit, the measurement is convenient and safe.
(7) It can calibrate voltmeter, ammeter, power meter, phase meter and other indicating instruments, and also can measure variety of 1A or 5A three-phase three-wire, three-phase four-wire and single phase of active and reactive energy meters.
(8) Can use photoelectric, manual, pulse and other methods to calibrate the energy meter.
(9) Measurement and analysis of the AC power quality from the grid to the client, can measure and analyze frequency deviation, voltage deviation, voltage fluctuation, three-phase voltage unbalance and harmonic.
(10) it can display the single-phase voltage, current waveform, it also can display the three-phase voltage and current waveform at the same time.
(11) Load fluctuation monitoring: measuring and analyzing the fluctuation of power quality caused by the power quality of the public power grid under different operating conditions. Recording and storage voltage, current, active power, reactive power, apparent power, frequency, phase and other power parameters.
(12) Dynamic monitoring the adjustment and operation of electrical equipment, to help users solve the problems occurred during adjustment and operation.
(13) With optional bar code scanner, can automatically enter the bar code of meter.
(14) Can test the communication interface 485 of energy meter, and also can make on-site calibration for multifunctional (intelligent) energy meter, can carry out error checking according to the demand cycle and slip time which has been set in the meter.
(15) With calendar and clock function, real-time display date and time.
(16) Can save the test results and on-site calibration at the same time, and uploaded to the computer through the serial port to realize computerized management of data by the backstage management software (optional). Reserved USB port, you can unload the stored data into U disk directly.
Parameters of the products
1, Operation temperature
Operation temperature: -10℃~ +40℃
2, Insulation
⑴, The insulation resistance between chassis and voltage input or current input: ≥ 100MΩ.
⑵, The withstand between the input end of working power supply and the casing is 1.5KV (RMS), for 1 minute experiment.
3, Current measuring range:0 ~ 5A. The built-in transformer is divided into 5A (CT) gear. Clamp-on transformer is divided into six gears, they are 5A (small clamp), 25A (small clamp), 100A (medium clamp), 500A (medium clamp), 400A (big clamp), 2000A (big clamp) . (the medium clamp and large clamp is optional).
4, Voltage measuring range 0 ~ 400V. 57.7V, 100V, 200V, 400V four gears of measuring range can be switched automatically.
Product introduction
NADS Multi-functional energy meter calibrator is the latest development of high precision testing instrument in our company, which has functions of electric parameter measurement, energy meter calibration and wiring judgment. The instrument is equipped with high precision and high linearity of voltage transformer and current transformer to make high measuring precision of various parameters, at the same time, it is equipped with clip-on current transformer, that makes the field wiring simple, it can directly access without interrupting current circuit.