* Used for outdoor substation, distribution device as well as high voltage electrical equipments
* System Voltage: 11kV, 33kV, 66kV(69kV), 132kV, 230kV, 400 kV
* Specified Cantilever Load (SCL):2-25 kN
* Color: Brown, Gray, or Customer's requirement
* Applicable Standard: IEC or Customer requirement
* Applicable Condition: environment temperature from -50℃ to +50℃,
altitude from 0 ~ 4000 meters above sea level, and medium &
heavy pollution area, especially for heavy earthquake areas.
Feature* High mechanical strength with much lower of deflection;
* Excellent performance of anti-pollution;
* Long lifetime is guaranteed;
* Maintenance expenditure is reduced to a minimum;
* Porcelain Core: manufactured with high alumina porcelain raw materials;
* Silicone Rubber Sheds: HTV silicone rubber, with alternative shed profile;
* With the high pressure injection molding at high temperature, the silicone
housing is fully bonded to the porcelain solid core which cemented fitting in
advance. The silicone housing adheres directly to the fitting without the
need for artificial sealing.
Main Dimension and Characteristics of Hybrid post Insulator
|
Type code |
Rated System voltage kV |
Mechanical Failing Load |
Dimension mm |
Creepage Distance mm |
Impulse With stand voltage kV |
Power- freq. Withstand voltage kV |
No.of unit |
|
|||
|
Bending kN |
Torsion kN.m |
|
|||||||||
|
H |
d |
Dry |
Wet |
|
|||||||
|
HP-C4-150-IV |
22kV |
6 |
1.5 |
355 |
94 |
750 |
150 |
80 |
50 |
1 |
|
|
HP-C4-325-IV |
66kV |
4 |
2 |
770 |
95 |
2500 |
325 |
170 |
140 |
1 |
|
|
HP-C4-550-IV |
132kV |
4 |
3 |
1220 |
115 |
4550 |
550 |
300 |
230 |
1 |
|
|
HP-C10-550-IV |
132kV |
10 |
4 |
1220 |
130 |
4500 |
550 |
300 |
230 |
1 |
|
|
HP-C6-650-IV |
145kV |
6 |
3 |
1500 |
130 |
5370 |
650 |
375 |
275 |
1 |
|
|
HP-C4-1050-IV |
245kV |
4 |
3 |
2300 |
130 |
7800 |
1050 |
495 |
460 |
2 |
|