Product Main

Quick Details

Application: Telecommunications
Type: On-line
Output Voltage: 100/110/115/120/127VAC or 200/208/220/230/240VAC
Weight: 4.6-28kg
Protection: Short Circuit
Phase: Single Phase
Model Number: 0002
Brand Name: upsen
Place of Origin: China (Mainland)

Specifications

Key Features 

? True double-conversion     
? Microprocessor control optimizes reliability     
? Input power factor correction     
? Output power factor 0.8    
? Wide input voltage (110 V – 300 V)
? Converter mode available    
? ECO mode for energy saving      
? Generator compatible     
? Charger capacity expansion to 6A for long-run models     
? Smart SNMP works well with either USB or RS-232 together    
? Comprehensive display allows easy monitoring and access of UPS status

 

 

Technical Specification

 

GREEN STAR ONLINE UPS SELECTION GUIDE
MODEL G1K (L) G2K (L) G3K (L)
PHASE Single phase with ground
CAPACITY 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W
INPUT
Nominal Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
Input Voltage Range  55-145 VAC or 110-300 VAC 
Frequency Range   40Hz  ~ 70 Hz
Power Factor ≧ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Output Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
Voltage Regulation  ± 1%
Frequency Range (Synchronized Range) 47~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦ 3 % THD (Linear Load); ≦ 6 % THD (Non-linear Load)
Transfer Time AC to DC Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
To AC Mode 88% 89% 90%
To Battery Mode 83% 87% 88%
BATTERY
Standard Model Battery Type 12 V / 9 AH 12 V / 7AH 12 V / 7 AH
Numbers 2 6 6
Typical Recharge Time 4 hours recover to 90% capacity
Charging Current (max.) 1.0 A
Charging Voltage 27.4VDC ± 1% 82.1 VDC ±1% 82.1 VDC ±1%
Long-run Model* Battery Type Depending on the capacity of external batteries
Numbers 3 6 8
Charging Current (max.) 1.0A/2.0A/4.0A/6.0 A
Charging Voltage 41.0VDC ± 1% 82.1 VDC ±1% 109.4VDC ±1%
INDICATORS
LCD

Load level, Battery level, AC mode, 

Battery mode, Bypass mode, and Fault indicators

ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding
PHYSICAL
Standard Model Dimension, D x W x H (mm) 397 X 145 X 220 419X190X318
Net Weight (kgs) 13 26 28
Long-run Model* Dimension, D x W x H (mm) 282 x 145 x 220 397 X 145 X 220
Net Weight (kgs) 4.6 6.8 7.4
ENVIRONMENT
Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser