Application: | Telecommunications |
---|---|
Type: | On-line |
Output Voltage: | 208/220/230/240VAC |
Weight: | 21kg |
Protection: | Overcurrent |
Phase: | Single Phase |
Model Number: | 0004 |
Brand Name: | upsen |
Place of Origin: | China (Mainland) |
Quick Details
Specifications
Key Features
? True double-conversion on line UPS
? DSP technology guarantees high performance
? Output power factor 0.8
? Active input power factor correction 0.99
? 50Hz/60Hz frequency converter mode
? Standard backup UPS and long backup UPS in one integrated unit
? Adjustable battery number from 16 pcs to 20 pcs
? Adjustable charging current via LCD or software (0.5A~6A)
? Wide input voltage range (110-300 VAC)
? Emergency power off function (EPO)
? 3-stage extendable charging design for optimized battery performance
? Maintenance bypass available
? SNMP/USB/RS-232 communications
Technical Specification
GREEN STAR 6K/10K ONLINE UPS SPECIFICATION | |||
MODEL | G6K (L) | G10K (L) | |
PHASE | 1 phase in / 1 phase out | ||
CAPACITY | 6000 VA / 4800 W | 10000 VA / 8000 W | |
INPUT | |||
Nominal Voltage | 208/220/230/240VAC | ||
Voltage Range | Low Line Loss |
110 VAC ± 3% at 50% Load 176 VAC ± 3% at 100% Load |
|
Low Line Comeback |
120 VAC ± 3% at 50% Load 186 VAC ± 3% at 100% Load |
||
High Line Loss | 300 VAC ± 3% | ||
High Line Comeback | 290 VAC ± 3% | ||
Frequency Range | 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz | ||
Power Factor | ≧ 0.99 @ 100% load | ||
OUTPUT | |||
Nominal Voltage | 208/220/230/240VAC | ||
AC Voltage Regulation | ± 1% | ||
Frequency Range (Synchronized Range) | 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz | ||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||
Current Crest Ratio | 3:1 (max.) | ||
Harmonic Distortion |
≦ 3 % THD (Linear Load) ≦ 6 % THD (Non-linear Load) |
||
Transfer Time |
Bypass to Inverter (Line mode) |
Zero | |
Inverter to Bypass (Line mode) |
Zero | ||
Waveform (Batt. Mode) | Pure Sinewave | ||
EFFICIENCY | |||
Line Mode | 89% | 90% | |
Battery Mode | 88% | 89% | |
BATTERY | |||
Standard Model | Battery Type | 12 V / 7 AH | 12 V / 9 AH |
Numbers | 16 | 16 | |
Typical Recharge Time | 9 hours recover to 90% capacity | ||
Charging Current |
Default:1.0 A ± 10%, Max.:2.0A ± 10% |
Default:1.0 A ± 10%, Max.:2.0A ± 10% |
|
Float Charging Voltage | 218.4 VDC ± 1% | ||
Long-run Model | Battery Type | Depending on applications | |
Numbers | 16-20** (adjustable) | ||
Charging Current | Default:4.0 A ± 10%, Max.:6.0A ± 10% |
Default:4.0 A ± 10%, Max.:6.0A ± 10% |
|
Float Charging Voltage | 273 VDC ± 1% (based on 20 pcs batteries) | ||
INDICATORS | |||
LCD Panel |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
||
ALARM | |||
Battery Mode | Sounding every 4 seconds | ||
Overload | Sounding twice every second | ||
Fault | Continuously sounding | ||
PHYSICAL | |||
Standard Model |
Dimension, D X W X H (mm) |
369 x 190 x 688 | 442 x 190 x 688 |
Net Weight (kgs) | 60 | 75 | |
Long-run Model |
Dimension, D X W X H (mm) |
369 x 190 x 318 | 442 x 190 x 318 |
Net Weight (kgs) | 21 | 23 | |
ENVIRONMENT | |||
Operation Humidity | 0-95 % RH @ 0- 40°C (non-condensing) | ||
Noise Level | Less than 55dBA @ 1 Meter |
Less than 58dBA @ 1 Meter |
|
MANAGEMENT | |||
Smart RS-232/USB |
Supports Windows? 2000/2003/XP/Vista/2008, Windows? 7/8, Linux, Unix, and MAC |
||
Optional SNMP | Power management from SNMP manager and web browser |