Product Main

Quick Details

Application: Networking
Type: On-line
Output Voltage: 110/120V
Weight: 12-32kg
Protection: Overvoltage
Phase: Single Phase
Model Number: 0005
Brand Name: upsen
Place of Origin: China (Mainland)

Specifications

Application
Network, data centre, servers and workstations, control system, communication system and office etc.

 

Key Features
1. Output power factor 0.9,offering more stronger load capability;
2. Online double conversion with DSP control 
    With excellent performance and comprehensive protections for load and UPS ; 
3. Self-diagnosis when UPS start up
4. Wide input range, support kinds of generator
5. Battery configuration flexible, 1KVA-24/36V, 2Kva-48/72/96V,3Kva-72/96V etc.
6. Cold start(DC power on)
7. ECO function, Economic function (Optional)
8. Compact design and less noise
9. Lightening and Surge protection 1050J
10. Fan speed varies according to load automatically
11. Smart RS232 (USB, Dry contact, SNMP card optional)
12. Manual bypass (optional)

 

Technical Specification

Model K1K K2K K3K
Capacity  Kva/Kw 1Kva/0.9Kw 2Kva/1.8Kw 3Kva/2.7Kw
Input Voltage Low transfer 85Vac± 3% (Ph-N) @100% load , 65Vac± 3% (Ph-N) @50% load
Low back  95Vac(Ph-N) @ 100% load ; 75Vac (Ph-N) @50% load
High transfer 110/120/127Vac:155V± 3%
High back  110/120/127Vac:142Vac± 3%
Frequency range 45-55Hz at 50Hz/55-65Hz at 60Hz(auto-detect)
Phase 1:1phase ,L+N+G
Current THDI <6%(100%nonlinear load)
Power Factor 0.99
Generate Input Support
breaker 7A 16A 25A
Output Voltage  110/120/127(1-3Kva)
Power Factor 0.9 (0.8 optional)
Voltage regulation ± 2%
Frequency(Line Model) 46-54Hz at 50Hz/56-64Hz at 60Hz
Frequency(Battery Mode)  50/60Hz ± 0.02Hz
Current Crest Ratio 3:01
Harmonic Distortion 3% THD(Liner Load)
5% THD(Non-Liner Load)
Output waveform Pure Sine wave
Outlet Sockets(Optional) Terminals
Overload Capacity 105%
Efficiency AC Mode Full Load89%
Battery Mode Full Load86%
ECO Mode Full Load95%
Battery Number of Battery Per Set 2004-2-3 2004-6-8 2004-6-8
Battery Type Sealed, lead-acid, maintenance-free 
standard model: 12V/7AH OR9AH inbuilt 
long run model: battery external, capacity optional
Back Time Standard unit: Standard unit: Standard unit:
5-12mins; 8-18mins; 5-12mins;
Long-run unit: Long-run unit: Long-run unit:
depends on external battery depends on external battery depends on external battery
Recharge Time(to 90%) 5 Hours 5 Hours 5 Hours
Charge Current(standard unit) 1.0A 1.0A 1.0A
Charge Current (long run unit) 7.0A 7.0A 7.0A
Rated Battery Voltage 24/36vdc 48/72/96vdc 48/72/96vdc
Protect Over-Voltage/Over-current/Low-voltage
Battery Socket Anderson like PowerPole Modular Connectors
Transfer Time Mains←→Battery 0ms
Mains←→Bypass 0ms
Optional Features Economic Mode(ECO Mode) Support
Indicator LCD Version (with LED) Load/Battery/Input/Output/Operating Mode Information etc.
Audible Alarm Battery Mode Sounding every 4 seconds
Low Frequency Sounding every second
Overload Sounding twice every second
Fault Continuously Sounding
Physical Unit Dimension (D*W *H)mm 420*144*215 475*191*340 475*191*340
Packing Dimension             (D*W *H)mm 524*258*334 557*286*435 557*286*435
Standard Unit Net /GrossWeight(kg) 12/13 30/32 30/32
Long-run unit Net /GrossWeight(kg) 7/8 15/17 15/17
Operating Environment 0-40°C
Relative Humidity 0-90%(non-condensing)
Altitude <1500m.when>1500m,derating
Noise Level <55db at 1 Meter
Interface Smart RS-232;USB,Dry contact board,SNMP(independent to RS232)

*Specification are subject to change without prior notice