Jacket: | PVC |
---|---|
Conductor Material: | Copper |
Application: | Construction |
Type: | Low Voltage |
Insulation Material: | XLPE |
Quick Details
Specifications
Product introduction
Product name: mineral insulated flexible BTLY (isolation) cable fire prevention
Specifications core core core (1, 2, 3, 4, 5, 3, 4, 3 + 2 + 1 core core core + 1)
1.product standards:
Standard fire flexible wiring according to the following:
Project |
GB/T |
IEC |
DIN VDE |
BS |
Cable insulation level and pressure rating |
12706 |
60502 |
||
Combustion test and mechanical test |
6027 |
|||
Flame spread test |
18380 .3 |
60332-3 |
0472 |
|
Flue gas divergent test |
17651.2 |
61034-2 |
0472 |
|
Circuit integrity test |
12666.6 |
60331 |
0472 |
6387 |
Halogen content test |
17650.2 |
60754-2 |
0472 |
|
Electrical cable fire test of the system |
4102 |
|
Test standard fire test
Fire flexible wiring design parameters, it is strictly follow the British BS6387 standards, and the
international electrotechnical commission IEC standards.The technical parameters, have been
respectively by the national fire administration and national fireproof construction material quality
supervision inspection center special detection.
Because fire cable are all with inorganic (copper and magnesium oxide powder), it itself does not cause
fire, impossible to burn or fire, as a result of the copper melting point is 1083 ℃, magnesia melting point
is 2800 ℃, so this kind of cable can be close to the melting point of copper fire cases continue to maintain
the power supply, is a real sense of fire retardant cable.
Test project |
BS6387 |
GB/T 12666.6 |
IEC331 |
Burn |
A(Level A): 650±40℃,180min B(Level B): 750±40℃,180min C(Level C): 950±40℃,180min S(Level S): 950±40℃,20min |
A(Type A): 950℃~1000℃90min B(Type B): 750℃~850℃90min |
750℃,3h |
Spray |
W(Level W): 650±40℃ Fire 15min, Fire again and spray15min burns for 15min, then burns again and sprays 15min |
No |
No |
Mechanical impact |
X(Level X): 650±40℃,15min Y(Level X): 750±40℃,15min Z(Level Z ): 950±40℃,30 times within 15min |
No |
No |
Note: DE exposure to fire flexible wiring has passed the highest level in international BS6387 standard C, W and Z test