Product Main

Quick Details

Main Circuit Rating Current: 630a
Main Circuit Rating Voltage: High Voltage
Model Number: HVJ6-12
Brand Name: Jucro
Place of Origin: China (Mainland)
Rated voltage: 12KV

Specifications

1.       Introduction

JCZ5 12 kv vacuum contactor

HVJ6-12 series indoor high-voltage AC vacuum contactor has two types: One is Mechanical holding type, the other is Electromagnetic holding type. It is applicable for three-phase AC 50HZ power system of rated voltage 12KV and below and rated current up to630Ato open and close circuit remotely and control electrical equipment like high-voltage motor, transformer and capacitive load. It is especially suitable for fields operated frequently. The contactor uses the international fashionable up and down structure  arrangement and has the advantages of small, light, easy to maintain and form a complete set of circuit equipment.

2. Service condition

a) Ambient air temperature: -25- +40.

b) Altitude not exceed2000m

c)Humidity:

-Relative humidity: daily mean not higher than95,monthly mean not higher than90;

-Aqueous vapor pressure: daily mean not exceed 2.2 KP, monthly mean not exceed 1.8 KP

Ambient air should not be obviously polluted by corrosive or flammable gas or vapor;

C)Free of frequent severe vibration; When running, angle of inclination between installation surface and horizontal plane should not exceed5.

 

Main technical parameters

Type

Rated voltage(V)

Rated current 

(Main circuit)(A)

Main contact parameter

Power frequency voltage resistance V(Effective value)

Main

circuit

Control

 circuit

Contacts separation (mm)

Overtravel(mm)

Main circuit

Auxiliary circuit

Control circuit

HVJ6-12/200

12000

110, 220

200

5+1-0.5

1.5±0.5

42000

2500

2000

HVJ6-12/400

12000

110, 220

400

5+1-0.5

1.5±0.5

42000

2500

2000

HVJ6-12/630

12000

110, 220

630

5+1-0.5

1.5±0.5

42000

2500

2000

 

Type

Making capability

Breaking capability

Limit breaking current(A)

Mechanical life times

Weight(KG)

HVJ6-12/200

10le,100 times

8le, 25 times

10le

30×104

32

HVJ6-12/400

10le,100 times

8le, 25 times

10le

30×104

32

HVJ6-12/630

10le,100 times

8le, 25 times

10le

30×104

32

 

 

TIPS:

1,nut

2,insulation framework

3,arc-extinguish chamber

4,softconnect

5,insulator

6,contact spring

7,connecting level

8,adjusting nut

9,magnet yoke

10,screw

11,baseboard

12,limit bolts

13,Opening spring

14, Iron core

15,coil

16,armature

17, square shaft

18, cover

19, latched device

20,cover

21,Terminal block XT