Model Number: | BS-898 |
---|---|
Place of Origin: | China (Mainland) |
Port Size: | DN65-DN150 |
Media: | Water |
Temperature of Media: | Medium Temperature |
Material: | Casting |
Pressure: | Medium Pressure |
Structure: | Ball |
Standard or Nonstandard: | Standard |
Quick Details
Specifications
(DN65-150) series electric regulating ball valve
Describe:
This series of products, adjustable flow ratio, high reliability, high life, the use of PTFE graphite reinforced body sealing ring, double EPDM valve stem sealing ring. Integrated built-in valve butterfly, not afraid of negative pressure. Equal percentage flow characteristic. High off force 1.4Mpa. Rated working pressure PN16. Maximum operating pressure of 0.35 Mpa. Short connect button with manual actuator. Working temperature of -5oC to 121oC. Suitable for water, steam or 50% ethylene glycol water.
Features and performance:
1. equal percentage flow characteristics
2. drive with different torque options
3.Three control modes: switch control, floating point control, or continuous adjustment
4. And actuator matching, connecting pieces and the valve body with 4 screws fixed
5. small size, large selection range, wide range of applications:
Technical parameter:
Dimension:
Describe:
This series of products, adjustable flow ratio, high reliability, high life, the use of PTFE graphite reinforced body sealing ring, double EPDM valve stem sealing ring. Integrated built-in valve butterfly, not afraid of negative pressure. Equal percentage flow characteristic. High off force 1.4Mpa. Rated working pressure PN16. Maximum operating pressure of 0.35 Mpa. Short connect button with manual actuator. Working temperature of -5oC to 121oC. Suitable for water, steam or 50% ethylene glycol water.
Features and performance:
1. equal percentage flow characteristics
2. drive with different torque options
3.Three control modes: switch control, floating point control, or continuous adjustment
4. And actuator matching, connecting pieces and the valve body with 4 screws fixed
actuator connecting pieces | DN65,DN80 | DN100,DN125 | DN150 |
Non spring return | 16Nm | 24Nm | 32Nm |
- Various forms of air treatment unit
- VAV variable air volume, desiccant fan coil unit
- Single fan unit
- Air preheating coil unit
- The roof type air conditioning unit
- Boiler - water chiller system
Technical parameter:
Model | DN |
(A-B)Way KV(m3/h) |
Bypass KV(m3/h) |
Rotation Angle | Allow the differential pressure |
2-Way (Kg) |
3Way (Kg) |
DN-65 | 65 | 63 | ------ | 0-90° | 0.35 | 4.5 | ------ |
DN-80 | 80 | 100 | ------ | 6.8 | ------ | ||
DN-100 | 100 | 160 | ------ | 8.1 | ------ | ||
DN-125 | 125 | 250 | ------ | 12.0 | ------ | ||
DN-150 | 150 | 400 | ------ | 18.8 | ------ |
Dimension:
Model |
Flange reference circle |
L(mm) | D(mm) | H(mm) | n-d |
DN-65 | 145 | 97 | 105 | 136 | 4-18 |
DN-80 | 160 | 108 | 125 | 140 | 8-18 |
DN-100 | 175 | 120 | 145 | 104 | 8-18 |
DN-125 | 200 | 145 | 175 | 115 | 8-18 |
DN-150 | 230 | 165 | 205 | 138 | 8-18 |