Type: | Vacuum |
---|---|
Model Number: | HVD7-40.5 |
Brand Name: | Jucro |
Place of Origin: | China (Mainland) |
Rated voltage: | 40.5KV |
Quick Details
Specifications
1. Introduction
HVD7 40.5 kv outdoor HV AC vacuum circuit breaker VCB has many visual advantages like reasonable design, fashionable appearance, high safety and reliability, simple maintenance, long electric life. It is the ideal upgraded products of 35KV outdoor oil circuit breakers.
HVD7-40.5 vacuum circuit breaker is applicable for three-phase power system of AC 50HZ.It is used to make and break the load current ,overload current and short-circuit current.
2. Applicable environment
3.1The ambient temperature should be-30℃~ +40℃(-40℃in the frosty area);
3.2Altitude should not exceed2000m(over2000mis plateau type);
3.3The wind pressure should not exceed 700Pa(equal to wind speed34m/s);
3.4Air pollution degree: Ⅲ,that of antifouling type:Ⅵ;
3.5The installation site should be free from the fire, explosion, chemical corrosion and serious vibration.
1. Main technical parameters
No. |
Item |
Unit |
Date |
|||||
1 |
Rated voltage |
KV |
40.5 |
|||||
2 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
KV |
95 |
|||
Wet test |
80 |
|||||||
Lightning impulse withstand voltage(peak value) |
185 |
|||||||
3 |
Rated current |
A |
1600 |
2000 |
||||
4 |
Rated short-circuit breaking current |
KA |
20 |
25 |
31.5 |
|||
5 |
Rated short-circuit making current(peak) |
KA |
50 |
63 |
80 |
|||
6 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
|||||
7 |
Rated short-time withstand current |
KA |
20 |
25 |
31.5 |
|||
8 |
Rated peak withstand current |
KA |
50 |
63 |
80 |
|||
9 |
Rated short-circuit duration |
S |
4 |
|||||
10 |
Rated control voltage |
V |
AC220,110;DC220,110 |
|||||
11 |
Rated short-circuit breaking current break times |
Times |
20 |
|||||
12 |
Full-break time |
ms |
≤80 |
|||||
13 |
Mechanical life |
Times |
10000 |
|||||