Model Number: | FN12-12 |
---|---|
Brand Name: | Jucro |
Place of Origin: | China (Mainland) |
Rated voltage: | 12KV |
Quick Details
Specifications
FN12-12D 12KV load break switch 630A 1000A
1. General
FN12-12D/630-50 indoor AC high voltage load break switch, rated voltage is 12KV, rated frequency is 50Hz. It is a kind of three phases high voltage switch equipment. It can be used to breaking- closing load current, closed current, charge current for no-load transformer and cable, closing short-circuit current. The Load break switch which assembleds earthing switch can sustain short-circuit current.
FN12-12DR/1000-31.5 indoor AC high voltage load break switch-fuse combination electrical appliance is a combinated indoor high voltage switch equipment which combinated by FKN12-12D load break switch and S□LAJ-12(XRNT□-12)high voltage limiting current fuse. This appliance can open any current up to short circuit current; Load break switch open working current, Fuse open short circuit current, combination open any current from working current to short circuit current, meantime Fuse makes the Load break switch opening through striking
2. Technical data Performance
NO |
Item |
Unit |
Data |
|
FN12-12d/630 |
FN12-12(R)D/125 |
|||
1 |
Rated voltage |
kv |
12 |
|
2 |
Rated frequency |
Hz |
50 |
|
3 |
Rated current |
A |
630 |
1000 |
4 |
1 min power frequency withstand voltage |
kv |
Earthing to earthing and between phase 75,isolation fracture 85 |
|
5 |
Light implus withstand voltage |
kv |
Earthing to earthing and between phase 42,isolation fracture 48 |
|
6 |
Rated thermal stable current |
kA |
20(4s) |
|
7 |
Rated peak withstand stably current |
kA |
50 |
|
8 |
Rated making current(peak) |
kA |
50 |
50 |
9 |
Rated breaking current (expected value) |
KA |
|
31.5 |
10 |
Rated shift current |
KA |
|
1.5 |
11 |
Breaking current |
kA |
1.8 |
|
12 |
Breaking off-load transformer capacity |
kVA |
1250 |
|
13 |
Rated cable charging current |
A |
10 |
|
14 |
Rated active load current breaking times |
Time |
>100 |
|
15 |
Ram touched load switch off time |
S |
|
<0.06 |
16 |
Earth switch thermal stable current |
kA |
|
20(2s) |
17 |
Earth switch thermal stable current (peak) |
kA |
50 |
50 |
18 |
Motor operation supply voltage |
V |
AC&DC 110, 220 |
3. Mechanical characteristics
No. |
Project |
Unit |
FN12-12D/630-20 |
FN12-12DR/100-31.5 |
1 |
Auxiliary contact opening distance |
mm |
>155 |
|
2 |
Three-phase points, closing over the same period |
ms |
<3 |
|
3 |
Just now speed |
m/s |
>2.8 |
2.80+0.4 |
4 |
Just closing speed |
m/s |
>3.8 |
|
5 |
The grounding switch fracture distance |
mm |
145 ± 5 |
|
6 |
Main circuit resistance |
μΩ |
<120 |
<300 |
7 |
Maximum operating torque |
N.m |
<160 |
<180 |