Model Number: | CZBT1-132 |
---|---|
Brand Name: | Tianan Electric |
Place of Origin: | China (Mainland) |
Application: | Emergency power supply |
Voltage rating: | High voltage |
Quick Details
Specifications
Service condition
1 Ambient condition
a. Altitude ≤ 1000m;
b. Ambient temperature
Range of temperature: -25℃~+40℃;
c. Wind speed (outdoor) ≤ 35m/s;
d. Relative humidity ≤ 90%(+25℃);
e. Installation spot
The place shall have no fire, explosion, chemical corrosion and exquisite vibration.
2 Move condition of the substation
a. Max. speed ≤ 30km/h,when road surface is flat;
b. Max. speed ≤ 10km/h, when road surface is not flat.
Note:
If the above condition can't satisfy requirements, customer can consult with
manufacturer to resolve it.
2. Technical parameters
1. Rated capacity of main transformer kVA5000,6300,8000,10000,12500,16000,20000,25000
2. Technical parameters of HV side switch equipment 2.1. Rated technical parameters of disconnector (Table 1)Table 1
No. |
Item |
Unit |
Parameter |
1 |
System voltage |
kV |
132 |
2 |
Rated voltage |
kV |
145 |
3 |
Rated frequency |
Hz |
50 |
4 |
Rated current |
A |
2000,1600 |
5 |
Rated 1min power frequency withstand voltage |
kV |
275 |
6 |
Rated lightning impulse withstand voltage |
kV |
650 |
7 |
Rated short time withstand current |
KA |
25,31.5,40 |
8 |
Rated short time withstand time |
s |
3 |
9 |
Rated peak withstand current |
kA |
63,80,100 |
Table 2
No. |
Item |
Unit |
Parameter |
||
1 |
System voltage |
kV |
132 |
||
2 |
Rated voltage |
kV |
145 |
||
3 |
Rated frequency |
Hz |
50 |
||
4 |
Rated current |
A |
2000 |
||
5 |
Rated 1min power frequency withstand voltage |
kV |
275 |
||
6 |
Rated lightning impulse withstand voltage |
kV |
650 |
||
7 |
Rated short time withstand current / time |
KA/s |
40/4 |
||
8 |
Rated peak withstand current |
kA |
100 |
||
9 |
Rated short circuit breaking current |
kA |
40 |
||
10 |
Rated short circuit making current |
kA |
100 |
||
11 |
DC component |
% |
40 |
||
12 |
Rated operation sequence |
|
O 0.3s CO 180s CO |
||
13 |
Opening time |
ms |
35±5 |
||
14 |
Closing time |
ms |
105±15 |
||
15 |
Breaking time |
ms |
≤60 |
||
16 |
Non-simultaneity between poles |
Closing |
ms |
≤5 |
|
Opening |
ms |
≤3 |
|||
17 |
Fracture no. of each pole |
nos |
1 |
||
18 |
Mechanical endurance |
Times |
≥6000 |
||
19 |
Full capacity continuous breaking times |
Times |
≥20 |
||
20 |
SF6 gas pressure (20℃) |
Rated value |
MPa |
0.60 |
|
Alarm value |
MPa |
0.55 |
|||
Locking value |
MPa |
0.50 |
|||
21 |
SF6 gas moisture content(μl/l) |
Acceptance value |
PPm |
≤150 |
|
Operation allowable value |
PPm |
≤300 |
|||
22 |
SF6 yearly gas leakage rate |
% |
≤0.5 |
||
23 |
Total weight of each circuit breaker |
kg |
2000 |
||
2.3. Parameters of current transformer (Table 3, table 4)
Table 3
Rated primary current |
150, 300, 500, 750, 1000, 1500, 2000 |
Rated secondary current |
5A |
Rated output capacity and accuracy level
|
See table 4 |
Table 4
Current ratio |
Rated output capacity VA |
Measure accuracy level |
Protection accuracy level |
150/5 300/5 500/5 750/5 1000/5 1500/5 2000/5 |
20 20 30 30, 40 40, 50 50 50 |
0.5 0.5 0.5 0.5 0.5 0.5 0.5 |
5P20 5P20 5P20 5P20 5P20 5P20 5P20 |
Note: (1) Straight-through type bushing current transformer is attached in the circuit breaker.
2.4.Parameters of lightning arrester(Table 5), parameters of neutral point lightning arrester(Table 6).Table 5
No. |
Item |
Unit |
Parameter |
1 |
System voltage |
kV |
132 |
2 |
Rated voltage |
kV |
150 |
3 |
Rated frequency |
Hz |
50 |
4 |
Nominal discharge current |
kA |
10 |
5 |
DC 1mA reference voltage |
kV |
≥245 |
6 |
Residual voltage under lightning impulse current (peak) |
kV |
≤435 |
7 |
Residual voltage under operation impulse current (peak) |
kV |
≤370 |
22 |
Residual voltage under steep wave impulse current (peak) |
kV |
≤490 |
Table 6
No. |
Item |
Unit |
Parameter |
1 |
System voltage |
kV |
132 |
2 |
Rated voltage |
kV |
90 |
3 |
Rated frequency |
Hz |
50 |
4 |
Nominal discharge current |
kA |
1.5 |
5 |
DC 1mA reference voltage |
kV |
≥140 |
6 |
Residual voltage under lightning impulse current (peak) |
kV |
≤260 |
7 |
Residual voltage under operation impulse current (peak) |
kV |
≤240 |
8 |
Residual voltage under steep wave impulse current (peak) |
kV |
/ |
3.Technical parameters of switch equipment on LV side(Table 7)
Table 7
No. |
Item |
Unit |
Parameter |
1 |
System voltage |
kV |
11.5 |
2 |
Rated voltage |
kV |
12 |
3 |
Rated frequency |
Hz |
50 |
4 |
Rated current |
A |
2000, 1600, 1250, |
5 |
Rated 1min power frequency withstand voltage |
kV |
42/48 |
6 |
Rated lightning impulse withstand voltage |
kV |
75/85 |
7 |
Rated short time withstand current |
kA |
40, 31.5, 25 |
8 |
Rated short time withstand time |
s |
4 |
9 |
Rated peak withstand current |
kA |
100, 80, 63 |
10 |
Rated short circuit breaking current |
kA |
40, 31.5, 25 |
11 |
Rated short circuit making current |
kA |
100, 80, 63 |
12 |
Rated operation sequence |
|
O 0.3s CO 180s CO |
13 |
Mechanical endurance |
Times |
≥10000 |
4.Sound level of the substation: ≤65 dB
Protection grade of enclosure of switch chamber: IP23(when the door for natural ventilation is open); IP43(when the door for natural ventilation is closed)