Product Main

Quick Details

Type: High Voltage
Model Number: LW36-72.5
Brand Name: Tianan Electric
Place of Origin: China (Mainland)
Arc-extinguishing medium: SF6
Voltage rating: High voltage
Application: Substation, outdoor
Installation: Fixed
Certificate: KEMA, ISO, CCC,etc
Standards: IEC, ANSI, GB, etc

Specifications

Product intruduction
LW36-72.5 self energy outdoor HV AC SF6 circuit breaker is an outdoor three phase porcelain column electrical equipment mainly used in AC 50Hz or 60Hz, 72.5kV electricity systems in extremely cold regions (for electric stations in general regions and extremly cold regions). This product can be operated frequently and used as connection circuit breaker.
Product performance
1. High performance- strong rated circuilating ability: strong short-circuit breaking alibility at 3150A, 40kA
2. Long service life-electrical endurance: 31.5kAx21 times; mechanical life: 6000 times without maintenance and upto 10000 after simple adjustment
3. High reliability- sharing the arc extinguishing compartment structure with LW36-126; great product internal insulation redundancy; over-all cast aluminum alloy frame adopted for the spring structure; simple structure and high reliability; suitable for frequent operations.
4. Reliable breaking performance
5. Reliable sealing performance; annual leakage of SF6 gas <0.5%
6.Meeting the requirements of hard running environments-suitable for class IV polluted places and -40oC~+40oC environments
7. Multi-structure froms-usually porcelain column type and hancart type
.
Main technical parameter

Serial No.  Name  Unit   Value
1 Rated voltage 
 
72.5
2 Rated power frequency withstand voltage (1min)
 

 
2.1 To earth kV 160
2.2 Across open contact kV 160+42
3 Rated lightning impulse withstand voltage 
 

 
3.1 To earth kV 380
3.2 Across open contact kV 380+59
4 Rated frequency Hz 50/60
5 Rated curent A 3150
6 Rated short-circuit breakering current (Isc) kA 40
7 Rated short-circuit making current (peak) kA 100/104
8 Rated hsort-time withstand current kA 40
9 Rated peak withstand current kA 100/104
10 Rated duration of short-circuit  s 4
11 Rated out of phase breaking current kA 10
12 Short-line fault breaking current kA 90%Isc,75%Isc
13 Double earth fault breaking current kA 34.8
14 Rated operating sequence
 
o-0.3s-CO-180s-CO
15 Number of rated short-circuit breaking current times 20
16 First pole to clear factor 
 
1.5
17 Rated line charging breaking current  A 10
18 Rated SF6 gas pressure (20oC gauge pressure) Mpa 0.4
19 Gas refilling alarm pressure Mpa 0.36
20 Operation locakout pressure Mpa 0.32
21 Annual leakage of SF6 gas % ≤0.5
22 Gas humidity content (L/L) (20oC at handover) L/L ≤150x10-6
23 Mechanical endurance Times 6000
24 Opening time ms ≤30
25 Closing -opening time  ms ≥70
26 Creepage distance mm ≥2585
27 Weight of SF6 gas filled for each CB kg 6/8
28 Weight of one set of CB kg 1300