| Type: | High Voltage |
|---|---|
| Model Number: | LW36-72.5 |
| Brand Name: | Tianan Electric |
| Place of Origin: | China (Mainland) |
| Arc-extinguishing medium: | SF6 |
| Voltage rating: | High voltage |
| Application: | Substation, outdoor |
| Installation: | Fixed |
| Certificate: | KEMA, ISO, CCC,etc |
| Standards: | IEC, ANSI, GB, etc |
Quick Details
Specifications
Product
intruduction
LW36-72.5 self energy outdoor HV AC SF6 circuit breaker is an outdoor three phase porcelain column electrical equipment mainly used in AC 50Hz or 60Hz, 72.5kV electricity systems in extremely cold regions (for electric stations in general regions and extremly cold regions). This product can be operated frequently and used as connection circuit breaker.
Product performance
1. High performance- strong rated circuilating ability: strong short-circuit breaking alibility at 3150A, 40kA
2. Long service life-electrical endurance: 31.5kAx21 times; mechanical life: 6000 times without maintenance and upto 10000 after simple adjustment
3. High reliability- sharing the arc extinguishing compartment structure with LW36-126; great product internal insulation redundancy; over-all cast aluminum alloy frame adopted for the spring structure; simple structure and high reliability; suitable for frequent operations.
4. Reliable breaking performance
5. Reliable sealing performance; annual leakage of SF6 gas <0.5%
6.Meeting the requirements of hard running environments-suitable for class IV polluted places and -40oC~+40oC environments
7. Multi-structure froms-usually porcelain column type and hancart type
.
Main technical parameter
LW36-72.5 self energy outdoor HV AC SF6 circuit breaker is an outdoor three phase porcelain column electrical equipment mainly used in AC 50Hz or 60Hz, 72.5kV electricity systems in extremely cold regions (for electric stations in general regions and extremly cold regions). This product can be operated frequently and used as connection circuit breaker.
Product performance
1. High performance- strong rated circuilating ability: strong short-circuit breaking alibility at 3150A, 40kA
2. Long service life-electrical endurance: 31.5kAx21 times; mechanical life: 6000 times without maintenance and upto 10000 after simple adjustment
3. High reliability- sharing the arc extinguishing compartment structure with LW36-126; great product internal insulation redundancy; over-all cast aluminum alloy frame adopted for the spring structure; simple structure and high reliability; suitable for frequent operations.
4. Reliable breaking performance
5. Reliable sealing performance; annual leakage of SF6 gas <0.5%
6.Meeting the requirements of hard running environments-suitable for class IV polluted places and -40oC~+40oC environments
7. Multi-structure froms-usually porcelain column type and hancart type
.
Main technical parameter
| Serial No. | Name | Unit | Value |
| 1 | Rated voltage |
|
72.5 |
| 2 | Rated power frequency withstand voltage (1min) |
|
|
| 2.1 | To earth | kV | 160 |
| 2.2 | Across open contact | kV | 160+42 |
| 3 | Rated lightning impulse withstand voltage |
|
|
| 3.1 | To earth | kV | 380 |
| 3.2 | Across open contact | kV | 380+59 |
| 4 | Rated frequency | Hz | 50/60 |
| 5 | Rated curent | A | 3150 |
| 6 | Rated short-circuit breakering current (Isc) | kA | 40 |
| 7 | Rated short-circuit making current (peak) | kA | 100/104 |
| 8 | Rated hsort-time withstand current | kA | 40 |
| 9 | Rated peak withstand current | kA | 100/104 |
| 10 | Rated duration of short-circuit | s | 4 |
| 11 | Rated out of phase breaking current | kA | 10 |
| 12 | Short-line fault breaking current | kA | 90%Isc,75%Isc |
| 13 | Double earth fault breaking current | kA | 34.8 |
| 14 | Rated operating sequence |
|
o-0.3s-CO-180s-CO |
| 15 | Number of rated short-circuit breaking current | times | 20 |
| 16 | First pole to clear factor |
|
1.5 |
| 17 | Rated line charging breaking current | A | 10 |
| 18 | Rated SF6 gas pressure (20oC gauge pressure) | Mpa | 0.4 |
| 19 | Gas refilling alarm pressure | Mpa | 0.36 |
| 20 | Operation locakout pressure | Mpa | 0.32 |
| 21 | Annual leakage of SF6 gas | % | ≤0.5 |
| 22 | Gas humidity content (L/L) (20oC at handover) | L/L | ≤150x10-6 |
| 23 | Mechanical endurance | Times | 6000 |
| 24 | Opening time | ms | ≤30 |
| 25 | Closing -opening time | ms | ≥70 |
| 26 | Creepage distance | mm | ≥2585 |
| 27 | Weight of SF6 gas filled for each CB | kg | 6/8 |
| 28 | Weight of one set of CB | kg | 1300 |