Product Main

Quick Details

Model Number: XGN75-12
Brand Name: Tianan Electric
Place of Origin: China (Mainland)
Voltage rating: Medium votlage
Insulation medium: SF6 gas
Installation: Free standing
Application: indoor
Enclosure material: Stainless steel
Protection degree: IP67
Standards: IEC, ANSI, GB
Certificate: ISO, TUV, KEMA

Specifications

General
The gas insulated switchgear designed for installation in transformer substation, industrial plants, and infrastructure & complies the most stringent requirement of
Safety in operation
Staff safety
Operation reliability
Smaller footprints
Reduced maintenance work
This switchgear conforms to IEC 62271-200 and all primary components employed therein are in accordance with the relevant standards.
It is designed to accommodate high performance vacuum circuitbreaker (VCB) which has been designed and tested in accordance with IEC62271-100.
The switchgear panels are suitable for the assembly of single &double busbar systems for indoor installation.
Features:-
1. Reliable
Each compartment is monitored individually &has its own pressure relief device.
Use of Vacuum circuit breakers with high number ofmechanical & electrical operations
Robust interlocking system
2. Safety
The primary side components are hermetically enclosed, gas filled compartment and thus insensitiveto atmosphere, dirt &dust.
Current transformer are mounted outside the gas compartment & mounted on earthed LV compartment
3. Space saving
Smaller foot prints. All operations on the switchgear front
4. Economically efficient
Reduced space & surface area requirement.
Long service life
Maintenance free Gas compartment
Technical Data

S/N Item  Unit Data
1 Rated voltage kV 12
2 Rated current A 630 1250 2000 2500
3 Rated frequency Hz 50/60
4 Rated power frequenecy withstand voltage (1 min)
 

 
5 Phase to phase, phase to earth kV 45
6 Between clearance kV 48
7 Rated ligtning impulse withstand voltage 
 

 
8 Phase to phase, phase to earth kV 75
9 Between clearance kV 85
10 Power frequency withstand voltage of auxiliary
control circuit (1 min)
V 2000
11 Rated short-cricuit breaking current (rms) kA 20 25 31.5
12 Rated short-circuti making current kA 63 80 100
13 Rated short time withstand current kA/s 25/4 31.5/4 40/4
14 Rated peak withstand current kA 63 80 100
15 Degree of protection
 
Gas-filled compartment : IP67
LV compartment: IP4X
16 Every phase amin return circuit resistance <250
17 Rated SF6 gas pressure (20oC) Mpa 0.045
18 Min SF6 gas pressure (20oC) Mpa 0.03
19 Annual SF6 gas loss rate % <1
20 Rated voltage of auxiliary control circuit  V DC 110/220
AC 220
21 Dimensions (WxDxH) mm 500x1000x1850