Product Main

Quick Details

Jacket: PVC
Conductor Material: Copper
Application: Construction
Type: Low Voltage
Insulation Material: PVC
sheath: PVC

Specifications

 

21/35KV XLPE Insulated Power Cables With Copper Conductor

1)      Type:

CU/XLPE/PE/FSWA/PE

2)      Standard:

IEC60502

3)      Construction

1: Solid or Stranded copper conductor

2: XLPE insulation

3: PE inner sheath

4: Fine Steel Wire Armour

5: PE outer sheath

4)      Application

For laying in water ,seabed and large difference of level, able to bear larger mechanical pressure and pulling force.

5)      Technical data

Max. Operating Temperature: 90°C

Short circuit Temperature:250°C  (Max.5 sec.)

Rated Voltage: 21/35KV

Core   Number

Nominal Cross Section mm2

Overall Dia. (Approx)

 mm

Netweight (Approx)

 Kg/m

Delivery length

 (m)

Insulation Nominal Thickness (mm)

Armouring Size

Recommending Current Rating

Steel wire dia. (mm)

In soil (A)

In air (A)

One

50

42.1

3035

1000

9.3

2.0

221

218

70

43.8

3352

1000

9.3

2.0

270

268

95

46.8

4176

1000

9.3

2.5

322

322

120

48.4

4567

1000

9.3

2.5

365

368

150

50.0

5000

1000

9.3

2.5

409

415

185

51.8

5453

1000

9.3

2.5

461

471

240

54.4

6255

1000

9.3

2.5

533

549

300

56.6

6998

1000

9.3

2.5

601

623

400

60.2

8270

1000

9.3

2.5

588

717

500

64.0

9544

1000

9.3

2.5

775

820

630

68.1

11155

1000

9.3

2.5

877

937

800

72.4

13158

1000

9.3

2.5

981

1058

Three

3×50

85.3

9974

1000

9.3

3.15

219

217

3×70

89.3

11096

1000

9.3

3.15

268

270

3×95

93.2

12322

1000

9.3

3.15

321

327

3×120

96.7

13519

1000

9.3

3.15

364

375

3×150

100.4

14914

1000

9.3

3.15

409

426

3×185

104.5

16461

1000

9.3

3.15

461

486

3×240

110.2

18811

1000

9.3

3.15

533

570

3×300

115.2

21272

1000

9.3

3.15

601

651

3×400

122.8

25206

1000

9.3

3.15

682

753