| Application: | Security / Monitoring / Alarm |
|---|---|
| Type: | On-line |
| Output Voltage: | 3 x 380VAC/400VAC (3Ph + N) |
| Protection: | Overvoltage |
| Phase: | Three Phase |
| Model Number: | Legend Strar Series LS33 10K-100K |
| Brand Name: | UPSEN |
| Place of Origin: | China (Mainland) |
| Acceptable Voltage Range: | 305VAC ~ 460VAC |
| Nominal Voltage: | 3 X 380VAC/400VAC (3pH + N) |
| Rated Frequency: | 50/60Hz |
Quick Details
Specifications
LCD display 3 phase input 3 phase output low frequency online ups
Model:Low Frequency Online UPS Legend Strar Series LS33 10K-100K(3Ph in/3Ph out)
Quickly View:
<1>Generator compatible
<2>True online double conversion
<3>IGBT and DSP technology
<4>Built-in isolation transformer
<5>Self-diagnosis/cold-start functions
<6>Optional N+X parallel redundancy
Key Features
1:Built-in isolation transforme
2:DSP technology guarantees high reliability
3:True galvanic isolation transformer design
4:IGBT inverter design and digital control technology
5:Intelligent battery management to prolong battery lifecycle
6:perfect for the most demanding and delicate of applications
7:True on-line double conversion design providing all power protection
8:Advanced network monitor function and support various of operation system
9:Pure-online double conversion technology, to provide the best quality of power supply
10:Can make sure the reliability and safety of the load and system due to the full protective function
11:Redundant fan design and independent ventilation enhance durable operation under harsh environment
Application
Data center, Industrial equipment,Financial and Securities,telecommunication,aviation,traffic,post service, Electronic Cash Registers,Electronic Test Equipment,Telecommunications Systems etc.
Technical Specification
Model:Low Frequency Online UPS Legend Strar Series LS33 10K-100K(3Ph in/3Ph out)
Quickly View:
<1>Generator compatible
<2>True online double conversion
<3>IGBT and DSP technology
<4>Built-in isolation transformer
<5>Self-diagnosis/cold-start functions
<6>Optional N+X parallel redundancy
Key Features
1:Built-in isolation transforme
2:DSP technology guarantees high reliability
3:True galvanic isolation transformer design
4:IGBT inverter design and digital control technology
5:Intelligent battery management to prolong battery lifecycle
6:perfect for the most demanding and delicate of applications
7:True on-line double conversion design providing all power protection
8:Advanced network monitor function and support various of operation system
9:Pure-online double conversion technology, to provide the best quality of power supply
10:Can make sure the reliability and safety of the load and system due to the full protective function
11:Redundant fan design and independent ventilation enhance durable operation under harsh environment
Application
Data center, Industrial equipment,Financial and Securities,telecommunication,aviation,traffic,post service, Electronic Cash Registers,Electronic Test Equipment,Telecommunications Systems etc.
Technical Specification
| LS33 Series 10K - 80Kva | ||||||
| MODEL | 10K | 20K | 30K | 40K | 60K | 80K |
| CAPACITY | 10KVA/8KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW |
| INPUT | ||||||
| Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||
| Acceptable Voltage Range | 305VAC ~ 460VAC | |||||
| Frequency | 46-54Hz or 56-64Hz | |||||
| INVERTER | ||||||
| Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||
| Precision |
Stationary: ±1% Transitory: ±5% (load variations 100-0-100%) |
|||||
| Frequency |
50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz |
|||||
| Max. Synchronisation Speed | ±1 Hz/s | |||||
| Waveform | Pure Sinewave | |||||
| Total Harmonic Distortion (THDv) |
<2% (Linear Load) <5% (Non-linear Load) |
|||||
| Phase Displacement |
120o ±1% (balanced load) 120o ±2% (imbalances 50% of the load) |
|||||
| Dynamic Recovery Time | 1 cycle at 98 % of the static value | |||||
| Admissible Overload | 110% for 10min; 150% for 60sec ; >160% for 200ms | |||||
| Admissible Crest Factor | 3:1 | |||||
| Admissible Power Factor | 0.6~1 (inductive or capacitive) | |||||
| Imbalance Output Voltage @ 100% Unbalanced Load | <1% | |||||
| Current Limit |
High overload, short-circuit: RMS Voltage Limit High Crest-Factor current: Peak Voltage Limit |
|||||
| STATIC BYPASS | ||||||
| Type | Solid state | |||||
| Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||
| Frequency | 50/60 Hz | |||||
| Activation Criterion | Microprocessor control | |||||
| Transfer Time | Zero | |||||
| Admissible Overload | 150% for 1 hour; 180% for 30sec; >200% for 200ms | |||||
| Transfer to Bypass | Immediate, for overloads above 160% | |||||
| Retransfer | Automatic after alarm clear | |||||
| MAINTENANCE BYPASS | ||||||
| Type | Without interruption | |||||
| Voltage | 3 x 400V (3Ph + N) | |||||
| Frequency | 50/60 Hz | |||||
| Overall Efficiency | 90% | 91% | 92% | 93% | ||
| 90% | 91% | 93% | 93% | |||
| BATTERY & CHARGER | ||||||
| Battery Type and Numbers | 12VDC x 16 pcs | 12VDC x 32 pcs (29~32 pcs adjustable) | ||||
| Nominal Battery Voltage | 192 VDC | 384 VDC (Based on 32pcs batteries) | ||||
| Charging Method | CC/CV | |||||
| Precision | ±1% | |||||
| Charging Current | Max.: 40 A | |||||
| Charging Voltage | 216 VDC | 432 VDC (Based on 32pcs batteries) | ||||
| PHYSICAL | ||||||
| Dimensions, D x W x H(mm) | 656 x 405 x 817 | 656 x 405 x 941 | 840 x 432 x 1140 | 975 x 554 x 1286 | ||
| Net Weight (Kgs) | 180 | 205 | 295 | 330 | 451 | 519 |
| * Product specifications are subject to change without further notice |
|
|
|
|
|
|